7. Connect appropriate signaling notification devices 

to [AC FAIL & BAT FAIL]  

(Fig. 1) 

supervisory relay outputs. 

Note:

When used in fire alarm, 

burglar alarm or access control applications, 
“AC Fail” relay must be used to provide a visual 
indication of AC power on.

Maintenance:

Unit should be tested at least once a year for the proper 
operation as follows:

Output Voltage Test:

Under normal load conditions, the DC

output voltage should be checked for proper voltage level

(refer to Power Supply Voltage Output Specification chart).

Battery Test:

Under normal load conditions check that the battery is fully charged, check specified voltage 

both at battery terminal and at the board terminals marked [+ BAT –] to insure there is no break in the 
battery connection wires.

Note:

Maximum charging current under discharge is 0.7 amp.

Note:

Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status 

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Function/Description

Legend

AC/AC

Connect 28VAC to these terminals from 2 connected in parallel transformers.

+ DC –

12VDC or 24VDC @ 6 amp continuous non-power limited output. 

AC FAIL

Used to notify loss of AC power, e.g. connect to annunciator/alarm 

NC, C, NO

panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 30VDC.  AC Fail condition will report approximately
one (1) to one minute after loss of AC. To delay report for 6 hours cut jumper J1 on the
Power Supply Board (AC trouble output delay option).  If this mode is selected the Power 
Supply Board must be reset by removing all power to it for 30 seconds.

BAT FAIL

Used to indicate low battery condition, e.g. connect to alarm panel.

NC, C, NO

Relay normally energized when DC power is present.
Contact rating 1 amp @ 30VDC.  Low battery conditions will report approximately 21VDC 
(24VDC output setting) or approximately 10.5VDC (12VDC output setting).  Battery presence 
detection will report approximately 1 minute after battery remains undetected
(missing or removed).

+ BAT –

Stand-by battery connections. Maximum charge current 1.2 amp.

Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL600ULB

G27J

MEMBER

+

DC ---

DC

AC

AC

+

BAT ---

OPEN = 24V SW1 CLOSED = 12V

RL2

RL3

AC

RLY1

PTC2

AC

TR

O

UB

LE

DE

LA

Y

O

PT

IO

N

IC3

IC2

AC

FA

IL

NC
C
NO

BA

T

FA

IL

NC
C
NO

Fig. 1