- 4 - 

AL300ULX Series

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 7, 8)

. Secure enclosure to earth ground. 

2. Set the unit to the desired DC output voltage by setting SW1

 (Fig. 1c, pg. 3)

 to the appropriate position 

 

(Power Supply Output Specification Chart, pg. 2).

3. Secure cabinet to earth ground. Connect AC power (115VAC, 60Hz to the terminals marked [L, N] 

 

(Fig. 1, pg. 3)

. Green “AC” LED on power supply board will turn on. This light can be seen through the 

  LED lens on the door of the enclosure. Use 14 AWG or larger for all power connections (Battery, DC output, 

  AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC fail/Low Battery reporting).

 

Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.

  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

  service personnel.

  For Fire Alarm applications the outputs are “Special Applications” only see list 

(refer to Appendix A, pg. 6)

  For other devices contact Underwriters Laboratories to ensure compatibility.

4. Measure output voltage before connecting device. This helps avoiding potential damage. 

  When servicing the unit, AC mains should be removed.

5. Connect devices to be powered:

  a. For AL300ULX Power Supply: connect devices to the terminals marked [+ DC –] 

(Fig. 1, pg. 3)

.

  b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked

    [1P & 1N] through [4P & 4N] 

(Fig. 2a & 2b, pg. 5)

 or 1 to 8 marked [1P & 1N] through [8P & 8N]

  

(Fig. 3a & 3b, pg. 5), 

carefully observing correct polarity.

6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

  Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation. 

  Use two (2) 12VDC batteries wired in series for 24VDC operation.

7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1a, pg. 3)

 supervisory 

  relay outputs.

 

Note:

 When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be

  utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper 

(Fig. 1b, pg. 3)

8. Please ensure that the cover is secured with the provided key lock.

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Содержание AL300ULPD4

Страница 1: ...X Series Power Supply Charger Models Include For a red enclosure add an R suffix to the part e g AL300ULPD8R Installation Guide AL300ULX Single Output AL300ULPD4 Four 4 Fuse Protected Outputs AL300ULP...

Страница 2: ...s UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment UL 1481 UL Listed for Power Supplies for Fire Protective Signaling Systems Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983...

Страница 3: ...tch Position 24VDC SW1 OFF 12VDC SW1 ON Battery AC Supervision Circuit power limited J1 AC Delay Green Lead 115VAC power mains non power limited Class 1 DC Output to devices power limited CAUTION When...

Страница 4: ...ualified service personnel For Fire Alarm applications the outputs are Special Applications only see list refer to Appendix A pg 6 For other devices contact Underwriters Laboratories to ensure compati...

Страница 5: ...by battery connections Maximum charge current 0 7A Power Distribution Module Terminal Legend Function Description PD4UL PD4ULCB PD8UL PD8ULCB 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to...

Страница 6: ...35o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 3...

Страница 7: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Страница 8: ...m 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27...

Отзывы: