AL300ULX Series 

- 3 -

Power Supply Output Specifications:

Output

Switch Position

12VDC

SW1 - ON

24VDC

SW1 - OFF

Stand-by Specifications 

(total current shown)

:

Output

4 hr. of Stand-by and

5 Minutes of Alarm

24 hr. of Stand-by and

5 Minutes of Alarm

60 hr. of Stand-by and

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 2.5A

24VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

ON

OFF - 24V

ON - 12V

L       G        

N

BAT FAIL  NC  C  NO  NC  C  NO 

 

AC  FAIL

AC

+ BAT -

+ DC -

DC

BAT

F1

Off - 24V

On - 12V

SW1

ON

Switch Position:

24VDC = SW1 OFF

12VDC = SW1 ON

Battery & AC

Supervision Circuit

(power-limited)

J1

AC Delay

Green

Lead

115VAC power mains

non power-limited

Class 1

DC Output to devices

(power limited)

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

For 12VDC Operation

use hook-up in the

inset on the right

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

Battery & AC

Supervision Circuit

(power-limited)

NC  C  NO NC  C  NO  

J1

AC Delay

OFF - 24V

ON - 12V

SW1

ON

1

CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.

Fig. 1 - 

AL300ULX

Fig. 1a

Fig. 1b

Fig. 1c

Содержание AL300ULPD4

Страница 1: ...X Series Power Supply Charger Models Include For a red enclosure add an R suffix to the part e g AL300ULPD8R Installation Guide AL300ULX Single Output AL300ULPD4 Four 4 Fuse Protected Outputs AL300ULP...

Страница 2: ...s UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment UL 1481 UL Listed for Power Supplies for Fire Protective Signaling Systems Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983...

Страница 3: ...tch Position 24VDC SW1 OFF 12VDC SW1 ON Battery AC Supervision Circuit power limited J1 AC Delay Green Lead 115VAC power mains non power limited Class 1 DC Output to devices power limited CAUTION When...

Страница 4: ...ualified service personnel For Fire Alarm applications the outputs are Special Applications only see list refer to Appendix A pg 6 For other devices contact Underwriters Laboratories to ensure compati...

Страница 5: ...by battery connections Maximum charge current 0 7A Power Distribution Module Terminal Legend Function Description PD4UL PD4ULCB PD8UL PD8ULCB 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to...

Страница 6: ...35o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 3...

Страница 7: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Страница 8: ...m 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27...

Отзывы: