background image

 

- 2 - 

AL125220 Series

Overview:

Altronix AL125220 and AL125X220 Power Supply/Chargers convert 220VAC (working range 198VAC - 256VAC), 

50/60Hz input into two individually PTC protected auto-resettable 12VDC or 24VDC outputs (see specifications). 

They are intended for use in Access Control applications and applications requiring an interface with Fire Alarm 

Control Panels.

Specifications:

*Note:

 

When unit is powered by battery back up (AC Fail condition), the voltage range is 9.3V-13.2V and 

 

19.55V-26.4V for 12 and 24 volt operation respectively. 

Power Supply Output Specifications:

Output VDC

Switch Position

Max. Stand-by

Load DC

Max. Alarm

Load DC

Battery

(optional)

12VDC

SW2 OFF

1A

1A

12VDC

24VDC

SW2 ON

1A

1A

24VDC

Stand-by Specifications:

Output

4hr. of Stand-by &

5 min. of Alarm

Output

4hr. of Stand-by &

5 min. of Alarm

12VDC / 4AH Battery

0.5A / 1A

12VDC / 7AH Battery

1A / 1A

24VDC / 4AH Battery

0.5A / 1A

24VDC / 7AH Battery

1A / 1A

Installation Instructions:

The units should be installed in accordance with article 760 of The National Electrical Code and NFPA 72 as 

well as all applicable Local Codes.

See Terminal Identification Chart on page 4 for a description of each terminal function.

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 7-8)

.

2. Power connections: Connect secondary (blue and yellow leads) from the transformer to the Power Supply 

  Board terminals marked [XFMR] 

(Fig. 1 - Application Diagram, pg. 5)

. Connect unswitched AC 

  circuit (220VAC, 50/60Hz) as follows: Green branch wire (ground) connects to the terminal marked     , 

  Line connects to the terminal marked [L], and Neutral connects to the terminal marked [N] of the Inlet 

  Appliance Connector.

Input:

•  220VAC (working range 198VAC - 256VAC), 

  50/60 Hz, 0.3A.

Output:

•  Two (2) 12VDC or 24VDC outputs.

•  1A total supply current @ 12VDC or 24VDC.

•  Filtered and electronically regulated output.

*

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current: 400mA.

•  Automatic switch over to stand-by battery when 

  AC fails.

Special Features:

•  AC power and unit status indicator on 

  the front panel.

•  Normally Open [NO] trigger input.

•  Supervised Fire Alarm Disconnect 

  (Latching w/reset or Non-Latching).

Enclosure Dimensions 

(H x W x D)

:

• AL125220:

 

  8.5” x 7.5” x 3.5”

  (215.9mm x 190.5mm x 88.9mm).

  Accommodates one (1) 12VDC/4AH battery.

• AL125X220:

 

  13.5” x 13” x 3.25”

  (342.9mm x 330.2mm x 82.6mm)

  Accommodates up to two (2) 12VDC/7AH batteries.

Door

XFMR

Status

Light

220VAC

50/60 Hz

0.3 amp

Input

White

Lead

Black

Lead

VR1

NO

NO

GND

GND

FACP1

FACP2

COM-

-

LOCK+

+ AUX 

--

TRIG

INPUT

RESET

SW1

+ BAT --

XFMR

Battery connections

(non power-limited)

DC Output to devices

(power-limited)

ON

ON

SW2:

OFF - 12VDC

ON - 24VDC

1A

250V

Содержание AL125220 Series

Страница 1: ...12VDC 4AH battery AL125X220 Includes power supply transformer cam lock and enclosure 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries Installation Guide Rev 102706 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install two fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 7 8 2 Power connections Connect secondary blue and yellow leads from the transformer to the Power Supply Board terminals...

Страница 3: ...by turning SW1 ON Fig 1 pg 5 and connect a normally open reset device to the terminals marked RESET NO GND 8 Connect battery to the terminals marked BAT battery leads included Use two 2 12VDC batteries connected in series for 24VDC operation Note For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of...

Страница 4: ...opped to the terminal marked LOCK and supplied to the terminal marked STRIKE RESET NO GND Momentary short between these terminals would end latching FACP interface condition Feature active only if latching FACP is selected SW1 ON BAT Stand by battery connections LED Diagnostics Red Power Supply Status ON Normal function OFF No DC output Slow Blink Loss of AC Rapid Blink Unit is triggered awaiting ...

Страница 5: ...ng Device Normally Open Reset Device 2 2K EOL supplied MAG LOCK NC FACP NO FACP Note If 2 2K resistor is not installed unit will be in alarm condition Card Reader ON ON Transformer Stand by Batteries 1 STRIKE COM LOCK AUX XFMR BAT SW2 OFF 12VDC ON 24VDC ON Transformer Stand by Batteries ELECTRIC STRIKE STRIKE COM LOCK AUX Application Diagram Fig 1a SW2 Fig 1 ...

Страница 6: ... 6 AL125220 Series Notes ...

Страница 7: ...90 5mm x 88 9mm 7 25 184 2mm 3 625 92mm 1 25 31 8mm 3 5 88 9mm 6 05 153 7mm 1 125 28 6mm 1 125 28 6mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 4mm 1 25 4mm 1 25 4mm 1 25 31 75mm 1 25 31 75mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 7mm 3 5 88 9mm ...

Страница 8: ...eries F29U MEMBER Enclosure Dimensions H x W x D AL125X220 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4...

Отзывы: