background image

 

AL125220 Series 

- 3 -

  Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs). 

  Use 22 AWG to 18 AWG for power-limited circuits (Trigger inputs, Dry outputs, DC outputs).

3. 

Measure output voltage before connecting devices. This helps avoiding potential damage.

4. Set the desired DC output voltage by setting switch SW2 to the appropriate position 

 

(Power Supply Output Specifications Table, pg. 2, Fig. 1a, pg. 5).

5. Connect Fail-Safe locking devices to the terminals marked [COM –] and [LOCK+]. 

  Connect Fail-Secure locking devices to the terminals marked [COM –] and [] (

Fig. 1, pg. 5). 

6. Connect normally open access control device (i.e. cardreader, request to exit device, access control system) 

  to the terminals marked TRG INPUT [NO, GND] (

Fig. 1 - Application Diagram, pg. 5).

7. Connect FACP interface to the terminals marked [FACP1] and [FACP2]. Wire the 2.2K resistor (supplied) 

  in series for a normally closed input or in parallel for a normally open input (

Fig. 1, pg. 5). 

If required, set 

  the latching FACP interface mode by turning SW1 ON 

(Fig. 1, pg. 5)

, and connect a normally open reset 

  device to the terminals marked RESET [NO, GND].

8. Connect battery to the terminals marked [+ BAT –] (battery leads included). 

  Use two (2) 12VDC batteries connected in series for 24VDC operation.

 

Note:

 For Access Control applications batteries are optional. 

  When batteries are not used, a loss of AC will result in the loss of output voltage. 

  When the use of stand-by batteries is desired, they must be lead acid or gel type.

9. Please ensure that the cover is secured with the provided cam lock.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked for proper 

 

voltage level

 (Power Supply Output Specifications Table, pg. 2).

Battery Test

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at battery terminal and at the board terminals marked [+ BAT –] to 

 

ensure that there is no break in the battery connection wires.

Note:

 

Maximum charging current under discharge is 400mA.

Note:

 

Expected battery life is 5 years; however, it is recommended changing batteries in 

 

4 years or less if needed.

Содержание AL125220 Series

Страница 1: ...12VDC 4AH battery AL125X220 Includes power supply transformer cam lock and enclosure 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries Installation Guide Rev 102706 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install two fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 7 8 2 Power connections Connect secondary blue and yellow leads from the transformer to the Power Supply Board terminals...

Страница 3: ...by turning SW1 ON Fig 1 pg 5 and connect a normally open reset device to the terminals marked RESET NO GND 8 Connect battery to the terminals marked BAT battery leads included Use two 2 12VDC batteries connected in series for 24VDC operation Note For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of...

Страница 4: ...opped to the terminal marked LOCK and supplied to the terminal marked STRIKE RESET NO GND Momentary short between these terminals would end latching FACP interface condition Feature active only if latching FACP is selected SW1 ON BAT Stand by battery connections LED Diagnostics Red Power Supply Status ON Normal function OFF No DC output Slow Blink Loss of AC Rapid Blink Unit is triggered awaiting ...

Страница 5: ...ng Device Normally Open Reset Device 2 2K EOL supplied MAG LOCK NC FACP NO FACP Note If 2 2K resistor is not installed unit will be in alarm condition Card Reader ON ON Transformer Stand by Batteries 1 STRIKE COM LOCK AUX XFMR BAT SW2 OFF 12VDC ON 24VDC ON Transformer Stand by Batteries ELECTRIC STRIKE STRIKE COM LOCK AUX Application Diagram Fig 1a SW2 Fig 1 ...

Страница 6: ... 6 AL125220 Series Notes ...

Страница 7: ...90 5mm x 88 9mm 7 25 184 2mm 3 625 92mm 1 25 31 8mm 3 5 88 9mm 6 05 153 7mm 1 125 28 6mm 1 125 28 6mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 4mm 1 25 4mm 1 25 4mm 1 25 31 75mm 1 25 31 75mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 7mm 3 5 88 9mm ...

Страница 8: ...eries F29U MEMBER Enclosure Dimensions H x W x D AL125X220 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4...

Отзывы: