AL1024NK8(D) Installation Guide)

LED Diagnostics:

AL1024ULXB2 - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by is battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PDS8(CB):

LED

ON

Green

12VDC Output.

Green and Red

24VDC Output.

Battery Size Calculation Worksheet:

A. AL1024NK8(D) internal current consumption 

(stand-by) 

________________  0.05 A

B. Load current consumption 

(stand-by) 

________________ A

C. Stand-by time required (hours) 

 

________________ H

D. Battery capacity required for stand-by 

(A+B)*C 

________________ AH

E. AL1024NK8(D) internal power consumption 

(Alarm) 

________________  0.05 A

F. Load current consumption 

(Alarm) 

________________ A

G. Alarm duration (Hours; 15 Min. = 0.25 Hour) 

(Alarm) 

________________ H

H. Battery capacity required for Alarm 

(E+F)*G 

________________ AH

I.  Total calculated battery capacity 

D+H 

________________ AH

J. Battery capacity required 

I*1.8 (safety factor)  ________________ AH

Note:

 AL1024NK8(D) power supply is designed to work with batteries up to 65AH. 

Please note: line [I] must not exceeds 36AH. 

You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size 

(e.g. 3.5 AH = 4.0 AH).

Содержание AL1024NK8 Series

Страница 1: ...ower selectable by output Eight 8 Class 2 power limited PTC protected outputs Built in Charger for sealed lead acid or gel type batteries AL1024NK8 Series Dual Output Power Supply Chargers Models Incl...

Страница 2: ...min of Alarm 4 hr of Stand by and 5 min of Alarm 24 hr of Stand by and 5 min of Alarm 60 hr of Stand by and 5 min of Alarm 24VDC 12AH Battery Stand By 8A Alarm 10A Stand By 1 5A Alarm 10A Stand By 200...

Страница 3: ...f each output is the same as the input voltage of the input selected Surge suppression Fuse PTC Ratings AL1024ULXB2 Input fuse is rated 5A 250V Battery fuse rated 15A 32V PDS8 Input fuse is rated 10A...

Страница 4: ...damage 5 Turn power off before connecting devices 6 Output Connections Connect devices to terminal pairs 1 to 8 marked P Positive OUT1 OUT8 N Negative on PDS8 CB carefully observing polarity 7 For Acc...

Страница 5: ...orted within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 2f pg 5 Bat Fail NC C NO Used to indicate low battery condition e g connect to alarm p...

Страница 6: ...capacity required for stand by A B C ________________ AH E AL1024NK8 D internal power consumption Alarm ________________ 0 05 A F Load current consumption Alarm ________________ A G Alarm duration Hou...

Страница 7: ...attery Output non power limited Supervisory connections power limited Spade Lugs to connect to the compatible board 24VDC from AL1024ULXB2 12VDC from VR6 factory connected Optional Rechargeable Stand...

Страница 8: ...8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Отзывы: