AL1024NK8(D) Installation Guide 

- 5 -

Fig. 2 - 

AL1024ULXB2 Board Configuration

2a

2b

2d

2c

2e

2f

L

G

N

BAT FAIL

AC FAIL

NC

C

NO

NC

C

NO

AC

DC

-   BAT   

+

+   DC   - 

AC DELAY

 

Terminal Identification:

AL1024ULXB2 - Power Supply Board

Terminal Legend

Function/Description

L, N

Connect 115VAC to these terminals: L to hot, N to neutral 

(Fig. 2a, pg. 5)

.

+ DC –

Factory connected to PDS8(CB) 

(Fig. 2d, pg. 5)

.

AC Fail

NC, C, NO

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 

AC or brownout fail is reported within 1 minute of event. 

To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 

(Fig. 2f, pg. 5)

.

Bat Fail

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 

A removed battery is reported within 1 minute. 

Battery reconnection is reported within 1 minute.

Low battery threshold: approximately 21VDC 

(Fig. 2b, pg. 5)

.

– BAT +

Stand-by battery connections. Maximum charge current 3.6A 

(Fig. 2c, pg. 5)

.

PDS8(CB):

Terminal Legend

Function/Description

+ INP1 –

Factory connected to AL1024ULXB2. Do not use these terminals.

+ INP2 –

Factory connected to AL1024ULXB2. Do not use these terminals.

P [OUT1-OUT8]

Positive DC power outputs.

N [OUT1-OUT8]

Negative DC power outputs.

Содержание AL1024NK8 Series

Страница 1: ...ower selectable by output Eight 8 Class 2 power limited PTC protected outputs Built in Charger for sealed lead acid or gel type batteries AL1024NK8 Series Dual Output Power Supply Chargers Models Incl...

Страница 2: ...min of Alarm 4 hr of Stand by and 5 min of Alarm 24 hr of Stand by and 5 min of Alarm 60 hr of Stand by and 5 min of Alarm 24VDC 12AH Battery Stand By 8A Alarm 10A Stand By 1 5A Alarm 10A Stand By 200...

Страница 3: ...f each output is the same as the input voltage of the input selected Surge suppression Fuse PTC Ratings AL1024ULXB2 Input fuse is rated 5A 250V Battery fuse rated 15A 32V PDS8 Input fuse is rated 10A...

Страница 4: ...damage 5 Turn power off before connecting devices 6 Output Connections Connect devices to terminal pairs 1 to 8 marked P Positive OUT1 OUT8 N Negative on PDS8 CB carefully observing polarity 7 For Acc...

Страница 5: ...orted within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 2f pg 5 Bat Fail NC C NO Used to indicate low battery condition e g connect to alarm p...

Страница 6: ...capacity required for stand by A B C ________________ AH E AL1024NK8 D internal power consumption Alarm ________________ 0 05 A F Load current consumption Alarm ________________ A G Alarm duration Hou...

Страница 7: ...attery Output non power limited Supervisory connections power limited Spade Lugs to connect to the compatible board 24VDC from AL1024ULXB2 12VDC from VR6 factory connected Optional Rechargeable Stand...

Страница 8: ...8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Отзывы: