- 2 - 

AL1024NK8(D) Installation Guide)

Overview:

Altronix AL1024NK8 and AL1024NK8D convert a 115VAC 60Hz input into eight (8) fuse or PTC protected 12VDC 

or 24VDC outputs with a total of 10A max. Dual input design allows power to be steered from two (2) factory 

installed independent low voltage 12 or 24VDC Altronix power supplies to eight (8) independently controlled fuse 

(AL1024NK8) or PTC (AL1024NK8D) protected outputs. 

Stand-by Specifications 

(total current shown)

:

Output

15 min. of Stand-by 

and 5 min. of Alarm

4 hr. of Stand-by 

and 5 min. of Alarm

24 hr. of Stand-by 

and 

5 min. of Alarm

60 hr. of Stand-by 

and 

5 min. of Alarm

24VDC/12AH 

Battery

Stand-By = 8A

Alarm = 10A

Stand-By = 1.5A

Alarm = 10A

Stand-By = 200mA

Alarm = 10A

Stand-By = 100mA

Alarm = 10A

Output

15 min. of Stand-by 

and 5 min. of Alarm

4 hr. of Stand-by and 

5 min. of Alarm

24 hr. of Stand-by 

and 15 min. of Alarm

60 hr. of Stand-by 

and 15 min. of Alarm

24VDC/65AH 

Battery

Stand-By = 8.0A

Alarm = 10A

Stand-By = 1.5A

Alarm = 10A

Stand-By = 500mA

Alarm = 10A

For Access Control applications, battery capacity for 10A supply current - 1 hr. for 24VDC/12AH battery,

6.5 hrs. for 24VDC/65AH battery.

See battery size calculation worksheet for other batteries 

(Page 6)

.

Содержание AL1024NK8 Series

Страница 1: ...ower selectable by output Eight 8 Class 2 power limited PTC protected outputs Built in Charger for sealed lead acid or gel type batteries AL1024NK8 Series Dual Output Power Supply Chargers Models Incl...

Страница 2: ...min of Alarm 4 hr of Stand by and 5 min of Alarm 24 hr of Stand by and 5 min of Alarm 60 hr of Stand by and 5 min of Alarm 24VDC 12AH Battery Stand By 8A Alarm 10A Stand By 1 5A Alarm 10A Stand By 200...

Страница 3: ...f each output is the same as the input voltage of the input selected Surge suppression Fuse PTC Ratings AL1024ULXB2 Input fuse is rated 5A 250V Battery fuse rated 15A 32V PDS8 Input fuse is rated 10A...

Страница 4: ...damage 5 Turn power off before connecting devices 6 Output Connections Connect devices to terminal pairs 1 to 8 marked P Positive OUT1 OUT8 N Negative on PDS8 CB carefully observing polarity 7 For Acc...

Страница 5: ...orted within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 2f pg 5 Bat Fail NC C NO Used to indicate low battery condition e g connect to alarm p...

Страница 6: ...capacity required for stand by A B C ________________ AH E AL1024NK8 D internal power consumption Alarm ________________ 0 05 A F Load current consumption Alarm ________________ A G Alarm duration Hou...

Страница 7: ...attery Output non power limited Supervisory connections power limited Spade Lugs to connect to the compatible board 24VDC from AL1024ULXB2 12VDC from VR6 factory connected Optional Rechargeable Stand...

Страница 8: ...8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Отзывы: