AL1012ULX Series

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 
2. Connect AC power (115VAC, 60 Hz) to the terminals marked [L, N] (Fig. 1, pg. 3). Green “AC” LED on 
  power supply board will turn on. This light can be seen through the LED lens on the door of the enclosure. 
  Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG 
  for power-limited circuits (AC Fail / Low Battery reporting).
  Note: Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input, 
  Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 
  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 
  service personnel.
3. Mea sure output voltage before connecting device. This helps avoiding potential damage. 
4. Connect devices to be powered:
  a.  For AL1012ULX: connect to the terminals marked [– DC +] (Fig. 1, pg. 3). 
 b. 

For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked  

    [1P & 1N] through [4P & 4N] (Fig. 2, pg. 5) or 1 to 8 marked [1P & 1N] through [8P & 8N] 
  (Fig. 3, pg. 5), carefully observing correct polarity.
5. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
6. Connect appropriate signaling notification devices to the terminals marked [AC FAIL & BAT FAIL] 
  (Fig. 1, pg. 3) supervisory relay outputs.
 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used 

  to  provide a visual indication of AC power on.
7. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper 
voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage 
both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the 
battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 

LED Diagnostics:

AL1012ULXB - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No power output.