M220 Series 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
 

in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all 

 screws 

(Enclosure Dimensions, pg. 15, 16). Secure enclosure to earth ground. 

 

It is recommended to first review the following tables for screw terminals, switch selection and 

 

LED status indications. This will greatly facilitate installation hook-up. 

 

Carefully review:

 

Output Voltage & Stand-by Specifications  (pg. 5) 

Terminal Identification Table  (pg. 10)

 

LED Diagnostics 

(pg. 4) 

Typical Application Diagrams  (pgs. 11 & 12)

2. 

Set output voltage:

 

AL300M220, AL400M220 (Fig. 1c, pg. 5) and AL600M220 (Fig. 2c, pg. 6): set desired DC output voltage 

 

by setting switch SW1 to the appropriate position on the power supply board. 

 

AL1012M220 is 12VDC only. AL1024M220 is 24VDC only. 

 

(Output Voltage and Stand-by Specification Charts, pg. 5).

3.  Secure green lead (earth ground) to ground lug. Connect AC power (115VAC, 60Hz) to the terminals 
 

marked [L, G, N] on power supply board (Figs. 1 - 4, pgs. 6 - 9)

 

Use 18 AWG or larger for all power connections (Battery, DC output, AC input).

 

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

4.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

5.  Connect Fail-Secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to 
 

terminals marked [1] through [5] [POS. (+) DC OUTPUT (ALARM)] on MOM5 board and the negative 

 

leads to terminals marked [NEG 1] through [NEG 5] on MOM5 board (Figs. 1 - 4, pgs. 6 - 9). 

6.  Connect Fail-Safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to 
 

terminals marked [6] through [10] [POS. (+) DC OUTPUT (STAND-BY)] on MOM5 board and negative 

 

leads to terminals marked [NEG 1] through [NEG 5] on MOM5 board (Figs. 1 - 4, pgs. 6 - 9). 

7.  To trigger the unit from a FACP connect signaling circuit of FACP to terminals marked [– INPUT +] on 
 

MOM5 board (Figs. 1 - 4, pgs. 6 - 9). Polarity is shown in alarm condition. 

 

For latching fire alarm interface see Fig. 7, pg. 11; Figs. 8 & 9, pg. 12.

 

Note: A 2.2K EOL must be installed across terminals marked [TRIGGER] on MOM5 board or the unit 

 

will remain in an alarm condition.

8.  To trigger the unit using a supervised dry contact connect the 2.2K resistor in series for a [NC] trigger 
 

input and in parallel for [NO] trigger input (Fig. 5, pg. 11).

9.  Connect auxiliary devices triggered by the unit to the terminals marked [DRY OUTPUT NO & C] on 
 

MOM5 board for normally open output or terminals marked [DRY OUTPUT NC & C] on MOM5 board 

 

for normally closed output (Figs. 1 - 4, pgs. 6 - 9). 

 

Note: This relay will energize when the unit is triggered.

10.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
 

in the loss of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery 

 

to terminals marked [+ BAT –] on power supply board for 12VDC operation (Figs. 1 - 4, pgs. 6 - 9).

 

Use two (2) 12VDC batteries connected in series for 24VDC operation. (Battery leads included).

11.  Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] and [Power Fail] 
 

supervisory relay outputs marked [NO, C, NC] on power supply board (Figs. 1a - 4a, pgs. 6 - 9). 

 

Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. 

 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be 

 

utilized to visually indicate that AC power is on. 

 

To delay report for 6 hours cut “AC Delay” jumper (Figs. 1b - 4b, pgs. 6 - 9).

12.  Please ensure that the cover is secured with the provided Key Lock.

Содержание AL1012M220

Страница 1: ...cess Control Power Supply Chargers Installation Guide Models Include AL300M220 2 5A 12VDC or 24VDC AL600M220 6A 12VDC or 24VDC AL1024M220 10A 24VDC AL400M220 4A 12VDC or 3A 24VDC AL1012M220 10A 12VDC...

Страница 2: ...bove Fire Alarm Panel or Access Control System trigger inputs NO or NC supervised trigger input and polarity reversal trigger input 4mA draw from FACP Output Five 5 individual PTC protected auto reset...

Страница 3: ...parts inside Refer installation and servicing to qualified service personnel 5 Connect Fail Secure type locking hardware e g door strikes and electronic dead bolts positive leads to terminals marked 1...

Страница 4: ...nt is 0 7A AL1024XB2V Power Supply Board maximum charge current is 3 6A Expected battery life is 5 years however it is recommended to change batteries within 4 years or less if necessary LED Diagnosti...

Страница 5: ...witch Position 4 hr of Stand by 5 Minutes of Alarm 24 hr of Stand by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 12VDC 40AH Battery ON Stand by 6 0A Alarm 6 0A Stand by 1 0A Alarm 6 0A Sta...

Страница 6: ...o Door Ground Lug Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery SW1 ON 1 OFF 24V ON 12V J1 AC Delay Battery AC Supervision Circuit NC C NO NC C NO Keep power limited wi...

Страница 7: ...und Lug Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery SW1 ON 1 OFF 24V ON 12V Battery AC Supervision Circuit NC C NO NC C NO Keep power limited wiring separate from non...

Страница 8: ...isture Keep power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting DC INPUT P...

Страница 9: ...p power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting DC INPUT POS DC OUTP...

Страница 10: ...3 6A MOM5 Output Module Terminal Legend Function Description DC INPUT 12VDC or 24VDC from power supply TRIGGER Dry normally open NO or normally closed NC supervised 2 2K EOL resistor input trigger A...

Страница 11: ...POWER FAIL TRIGGER NEG INPUT POS EOL 2 2K DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE N C INPUT FROM FACP OR ACCESS CONTROL DEVICE TRIGGER NEG INPUT POS EOL 2 2K DC VOLTAGE IN...

Страница 12: ...TRIGGER LED TRIGGER DC INPUT NEG INPUT POS POWER ON LED TRIGGER LED TRIGGER DC INPUT NEG INPUT POS POWER ON LED N O RESET EOL 2 2K EOL 2 2K DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTR...

Страница 13: ...rm A G Alarm duration Alarm H Hours example 15 Min 0 25 Hour H Battery capacity required for Alarm E F G AH0 I Total calculated battery capacity D H AH J Battery capacity required I 1 8 safety factor...

Страница 14: ...14 M220 Series Notes...

Страница 15: ...m x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm...

Страница 16: ...W x D for AL1012M220 AL1024M220 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114...

Отзывы: