background image

 

- 2 - 

M220 Series

Overview:

Altronix M220 Series multi-output access control power supply/chargers are specifically designed for use with 
access control systems and accessories. These units convert a 220VAC (working range 198VAC - 256VAC), 
50/60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see specifications). Each output 
will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic 
Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input 
is achieved through normally open [NO] or normally closed [NC] supervised input or the polarity reversal from 
an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or 
may be used to trigger auxiliary devices.

M220 Series Power Supply Configuration Reference Chart:

Altronix 
Model Number

12VDC Total

Output

Current (A)

24VDC Total 

Output

Current (A)

PTC Protected 

Outputs 

(auto-resettable)

220VAC

50/60Hz 

Input 

Current

Draw (A)

Power Supply 

Board Input 

Fuse Rating

AL300M220

2.5

2.5

5

1A

5A/250VAC

AL400M220

4

3

1.2A

AL600M220

6

6

1.5A

AL1012M220

10

2.2A

AL1024M220

10

3A

6.3A/250VAC

Specifications:

Input:

•  Power input 220VAC (working range 198VAC - 
 256VAC), 50/60Hz.
  See reference chart above.
•  Fire Alarm Panel or Access Control System trigger 
  inputs. [NO] or [NC] supervised trigger input and 
  polarity reversal trigger input 
  (4mA draw from FACP). 

Output: 

•  Five (5) individual PTC protected auto-resettable 
  power outputs.
•  Current limit is 2A @ 12VDC or 24VDC per output 
  (12VDC only for AL1012M220 and 
  24VDC only for AL1024M220).
•  Filtered and electronically regulated outputs.
•  Thermal and short circuit protection with auto reset. 
•  Overload protection.
•  Output relay energizes when unit is triggered 
  (form “C” contact rated 1A @ 28VDC).

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Automatic switch over to stand-by battery 
  when AC fails.
•  AL300XB220, AL400XB220, AL600XB220, and
  AL1012XB220 (Power Supply Board) maximum
  charge current 0.7A. 
  AL1024XB220 (Power Supply Board) maximum 
  charge current 3.6A.

Battery Backup 

(cont’d)

•  Zero voltage drop when switching over to 
  battery backup.
•  AL300M220, AL400M220, and AL600M220 
  enclosures accommodate up to 
  two (2) 12VDC/7AH batteries.
•  AL1012M220 should be fitted with 
  one (1) 12VDC/12AH battery.
•  AL1024M220 enclosure accommodates 
  up to two (2) 12VDC/12AH batteries.

Visual Indicators:

•  DC output LED indicator.
•  LEDs indicate condition of power outputs.
•  Power and input trigger LEDs.

Supervision:

•  AC fail supervision (form “C” contact). 
•  Low battery supervision (form “C” contact). 
•  Battery presence supervision (form “C” contact).
•  Power fail supervision relay 
  (form “C” contact rated 1A @ 28VDC).
•   Power supply is complete with enclosure, 
  cam lock, and battery leads.

Содержание AL1012M220

Страница 1: ...cess Control Power Supply Chargers Installation Guide Models Include AL300M220 2 5A 12VDC or 24VDC AL600M220 6A 12VDC or 24VDC AL1024M220 10A 24VDC AL400M220 4A 12VDC or 3A 24VDC AL1012M220 10A 12VDC...

Страница 2: ...bove Fire Alarm Panel or Access Control System trigger inputs NO or NC supervised trigger input and polarity reversal trigger input 4mA draw from FACP Output Five 5 individual PTC protected auto reset...

Страница 3: ...parts inside Refer installation and servicing to qualified service personnel 5 Connect Fail Secure type locking hardware e g door strikes and electronic dead bolts positive leads to terminals marked 1...

Страница 4: ...nt is 0 7A AL1024XB2V Power Supply Board maximum charge current is 3 6A Expected battery life is 5 years however it is recommended to change batteries within 4 years or less if necessary LED Diagnosti...

Страница 5: ...witch Position 4 hr of Stand by 5 Minutes of Alarm 24 hr of Stand by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 12VDC 40AH Battery ON Stand by 6 0A Alarm 6 0A Stand by 1 0A Alarm 6 0A Sta...

Страница 6: ...o Door Ground Lug Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery SW1 ON 1 OFF 24V ON 12V J1 AC Delay Battery AC Supervision Circuit NC C NO NC C NO Keep power limited wi...

Страница 7: ...und Lug Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery SW1 ON 1 OFF 24V ON 12V Battery AC Supervision Circuit NC C NO NC C NO Keep power limited wiring separate from non...

Страница 8: ...isture Keep power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting DC INPUT P...

Страница 9: ...p power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting DC INPUT POS DC OUTP...

Страница 10: ...3 6A MOM5 Output Module Terminal Legend Function Description DC INPUT 12VDC or 24VDC from power supply TRIGGER Dry normally open NO or normally closed NC supervised 2 2K EOL resistor input trigger A...

Страница 11: ...POWER FAIL TRIGGER NEG INPUT POS EOL 2 2K DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE N C INPUT FROM FACP OR ACCESS CONTROL DEVICE TRIGGER NEG INPUT POS EOL 2 2K DC VOLTAGE IN...

Страница 12: ...TRIGGER LED TRIGGER DC INPUT NEG INPUT POS POWER ON LED TRIGGER LED TRIGGER DC INPUT NEG INPUT POS POWER ON LED N O RESET EOL 2 2K EOL 2 2K DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTR...

Страница 13: ...rm A G Alarm duration Alarm H Hours example 15 Min 0 25 Hour H Battery capacity required for Alarm E F G AH0 I Total calculated battery capacity D H AH J Battery capacity required I 1 8 safety factor...

Страница 14: ...14 M220 Series Notes...

Страница 15: ...m x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm...

Страница 16: ...W x D for AL1012M220 AL1024M220 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114...

Отзывы: