ACM220 Series Installation Guide
Typical Application Diagram:
LED Diagnostics:
Power Supply Board
LED
Power Supply Status
Red (DC)
Green (AC)
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output.
Red (Bat)
Battery Status
ON
Normal operating condition.
OFF
Battery fail/low battery.
ACM8 Access Power Controller
LED
ON
OFF
LED 1 - LED 8 (Red)
Output relay(s) energized.
Output relay(s) de-energized.
Trg (Green)
FACP input triggered (alarm condition).
FACP normal (non-alarm condition).
NC
NO
C
Normally Open (N.O.)
Door Releasing
Device
Access Control Panel
Output
Relay
Mag.
Lock
MAG. LOCK
Electric
Strike
Electromagnetic
Door Holders
FACP
(Fire Alarm
Control
Panel)
UL Listed
Power Supply
For this application
corresponding
fuse F8 must be
removed.
Keypad
AC or DC
Power
Supply
(req'd.)
AC or DC
Power
Supply
(optional)
NC C NO COM
OUTPUT 1
LED1
F1
NC C NO COM
OUTPUT 2
IN GND
1
IN GND
2
IN GND
3
IN GND
4
IN GND
5
IN GND
6
IN GND
7
MAIN
IN GND
8
LED2
LED3
LED4
LED5
LED6
LED7
LED8
J2
TRG
FACP
NC C NO COM
OUTPUT 3
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 5
NC C NO COM
OUTPUT 6
NO C NC
+ INP
---
T +
RET
-
NC C NO COM
OUTPUT 7
NC C NO COM
OUTPUT 8
---
+
Power
---
+
Control
F2
F3
F6
F7
F8
F4
F5
J1
J3
TRG
FACP
FACP INTERFACE
10A 250V
FACP Dry
Form "C" Output
NO C NC
FACP
Intact = Dry Input
Cut = Wet Input
1 2 3 4
O N
1 2 3 4
O N
Enabled
Disabled
FACP Interface
SW1-SW8
ON
1
ON
1
J2
---
+
Control
J1
Intact = One P/S Input
Cut = Dual P/S Input
NC C NO COM
OUTPUT 8
J3
Intact = DC Input
Cut = AC Input
Fig. 1
Fig. 1b
Fig. 1a
Fig. 1c
Fig. 1d
Содержание ACM220 Series
Страница 11: ...ACM220 Series Installation Guide 11 Notes...