- 2 -
ACM220 Series Installation Guide
Overview:
Altronix ACM220 Series units distribute and switch power to access control systems and accessories. They convert
a nominal 220VAC (working range 198VAC - 256VAC), 50/60Hz input into eight (8) independently controlled 12VDC
or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C” contacts. Outputs are acti-
vated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader,
Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag
Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes.
The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices.
The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACM220 Series Configuration Reference Chart:
Altronix
Model Number
12VDC
Total
Output
Current
24VDC
Total
Output
Current
Fused
Outputs
Individual
Output
Rating
220VAC
50/60Hz
Input
Current
Draw
Power
Supply
Board
Input
Fuse Rating
Power
Supply
Board
Battery
Fuse Rating
AL400ACM220
4A
3A
8
3.5A
1.2A
5A/250V
15A/32V
AL600ACM220
6A
6A
1.5A
–
AL1012ACM220
10A
–
2.2A
15A/32V
AL1024ACM220
–
10A
3A
Specifications:
Input:
• Power supply input options:
a) One (1) common power input for ACM8 and
lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8 and one (1) for lock accessory power
(external power supply is required). Current is
determined by the power supply connected,
not to exceed a maximum of 10A total.
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 12VDC or 24VDC outputs.
• Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure
power
outputs.
b) Eight (8) form “C” 5A rated relay outputs
c) Any combination of the above.
• Eight (8) auxiliary power outputs (unswitched)
• Output fuses are rated @ 3.5A.
• Filtered and electronically regulated outputs
(built-in power supply).
Visual Indicators:
• Red LEDs indicate outputs are triggered
(relays energized).
• Green LED indicates FACP disconnect is triggered.
• AC input and DC output LED indicators.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• AL400XB2V, AL600XB220, and AL1012XB220
(Power Supply Board) maximum charge current 0.7A.
AL1024XB2V (Power Supply Board) maximum
charge current 3.6A.
• Automatic switch over to stand-by battery when
AC fails.
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to
battery backup (AC failure condition).
• Battery fail and battery presence supervision
(form “C” contact).
Features:
• Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
• Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1A 28VDC).
• Short circuit and thermal overload protection.
Enclosure Dimensions
(H x W x D approx.)
:
• 15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm)
• Enclosure accommodates up to
two (2) 12AH batteries.