ACM220 Series Installation Guide 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all 

 screws 

(Enclosure Dimensions, pg. 12)

. Secure enclosure to earth ground. 

 

It is recommended to first review the following tables to facilitate installation: 

 

Output Voltage and Stand-by Specifications Charts 

(pg. 3)

 

Typical Application Diagram 

(pg. 6)

 

LED Diagnostics 

(pg. 6)

 

Terminal Identification Tables 

(pg. 5)

 

Hook-up Diagrams 

(pg. 8-9)

2. 

Set output voltage:

 

AL400ACM220 and AL600ACM220: set desired DC output voltage by setting switch SW1 to the 

 

appropriate position on the power supply board. AL1012ACM220 is factory set at 12VDC and 

 

AL1024ACM220 is factory set at 24VDC 

(Output Voltage and Stand-by Specification Charts below).

Output Voltage and Stand-by Specification Charts:

AL400ACM220

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 

5 mins. Alarm

24 hr. Stand-by / 

5 mins. Alarm

12VDC

SW1 - ON

40AH

3.5A / 3.5A

1A / 3.5A

24VDC

SW1 - OFF

40AH

2.75A / 2.75A

1A / 3A

AL600ACM220

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 

5 mins. Alarm

24 hr. Stand-by / 

5 mins. Alarm

12VDC

SW1 - ON

40AH

5.5A / 5.5A

0.5A / 5.5A

24VDC

SW1 - OFF

40AH

5.75A / 5.75A

0.75A / 5.75A

AL1012ACM220

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 

5 mins. Alarm

24 hr. Stand-by / 

5 mins. Alarm

12VDC

N/A

40AH

9.5A / 9.5A

0.5A / 9.5A

AL1024ACM220 

(refer to AL1024ACM220 Battery Size Calculation Worksheet, pg. 10).

Voltage

Stand-by 

Battery

15 mins. Stand-by /

5 mins. Alarm

4 hr. Stand-by /

5 mins. Alarm

24 hr. Stand-by /

5 mins. Alarm

60 hr. Stand-by /

5 mins. Alarm

24VDC

12AH

7.7A / 9.7A

1.2A / 9.7A

24VDC

65AH

7.7A / 9.7A

1.2A / 9.7A

200mA / 9.7A

3. 

Connect AC 

(Fig. 2, pg. 7)

:

 

Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, N]. 

 

Use 14 AWG or larger for all power connections. Secure green wire lead to ground lug. 

 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

4.  Measure voltage before connecting devices. This helps avoiding potential damage.

Содержание ACM220 Series

Страница 1: ...______________ Phone ___________________ ACM220 Series Access Power Controllers with Power Supplies Models Include For a red enclosure add an R suffix to the part e g AL1024ACMR220 Installation Guide...

Страница 2: ...Current is determined by the power supply connected not to exceed a maximum of 10A total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open col...

Страница 3: ...t 24VDC Output Voltage and Stand by Specification Charts below Output Voltage and Stand by Specification Charts AL400ACM220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr St...

Страница 4: ...onding switch SW1 SW8 OFF To disable FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6...

Страница 5: ...it BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 m...

Страница 6: ...Strike Electromagnetic Door Holders FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypad AC or DC Power Supply req d AC or DC Power Su...

Страница 7: ...F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Fire Alarm Interface DC Output to Devices Battery and AC Supervision Circuit Observe Polarity Inputs Ground Lug U...

Страница 8: ...olarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER...

Страница 9: ...RG FACP Fig 7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching tr...

Страница 10: ...nsumption Alarm __________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm __________ H H Battery capacity required for Alarm E F G __________ AH I Total calculated battery capacity D H ______...

Страница 11: ...ACM220 Series Installation Guide 11 Notes...

Страница 12: ...nclosure Dimensions H x W x D approximate 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1...

Отзывы: