ACM Series 

- 3 -

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 

all local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 12). Secure enclosure to earth ground. 

 

It is recommended to first review the following tables to facilitate installation: 

 

Output Voltage and Stand-by Specifications Charts 

(pg. 2)

 

Typical Application Diagram 

(pg. 6)

 

LED Diagnostics 

(pg. 6)

 

Terminal Identification Tables 

(pg. 5)

 

Hook-up Diagrams 

(pg. 8-9)

2. 

Set output voltage:

 

AL400ULACM and AL600ULACM: set desired DC output voltage by setting switch SW1 to the appropriate

 

position on the power supply board. AL1012ULACM is factory set at 12VDC and AL1024ULACM is 

 

factory set at 24VDC (Output Voltage and Stand-by Specification Chart, pg. 2).

3. 

Connect AC (Fig. 2, pg. 7):

 

Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, N]. Use 14 AWG or larger for all 

 

power connections. Secure green wire lead to earth ground. Green “AC” LED on power supply board will 

 

turn on. This light can be seen through the LED lens on the door of the enclosure. 

 

Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

4.  Measure voltage before connecting devices. This helps avoiding potential damage.

Input:

•  Power input 115VAC, 60Hz 

 (see 

ACM Series Power Supply Configuration 

  Reference Chart, pg. 2).

• 

ACM8 Power Input Options:

  a) One (1) common power input for ACM8 and 

    lock power (factory installed).

  b) Two (2) isolated power inputs 

    (external power supply is required).

    Current is determined by the power supply 

    connected, not to exceed a maximum of 10A total.

•  Eight (8) Access Control System trigger inputs.

  Input options:

  a) Eight (8) normally open (NO) inputs.

  b) Eight (8) open collector inputs.

  c) Any combination of the above.

Outputs: 

•  Eight (8) independently controlled outputs.

  Output Options:

  a) Eight (8) Fail-Safe and/or Fail-Secure 

  power 

outputs.

  b) Eight (8) form “C” 5A rated relay outputs.

  c) Any combination of the above.

•  Eight (8) auxiliary power outputs (unswitched). 

•  ACM8 output fuses are rated 3.5A.

•  ACM8 board main fuse is rated at 10A.

•  Fire Alarm disconnect (latching or non-latching) is 

  individually selectable for any or all of the 

  eight (8) outputs.

•  Fire Alarm disconnect input options:

  a) Normally open (NO) or normally closed (NC) 

    dry contact input.

  b) Polarity reversal input fromFACP signaling circuit.

Outputs 

(cont’d)

•  Alarm output relay indicates that FACP input is 

  triggered (form “C” contact rated @ 1A 28VDC, 

  not evaluated by UL).

•  Filtered and electronically regulated outputs.

•  Thermal and short circuit protection with auto reset. 

Visual Indicators:

•  Green LED indicates when FACP disconnect 

  is triggered.

•  Red LEDs indicate outputs are triggered 

  (relays energized).

•  AC input and DC output LED indicators.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Automatic switch over to stand-by battery when 

  AC fails.

•  Zero voltage drop when switching over to 

  battery backup.

Supervision:

•  AC fail supervision (form “C” contact). 

•  Low battery supervision (form “C” contact). 

•  Battery presence supervision (form “C” contact).

•  Power fail supervision relay 

  (form “C” contact rated 1A @ 28VDC).

Enclosure Dimensions:

  15.5” x 12” x 4.5”

  (393.7mm x 304.8mm x 114.3mm).

  Enclosure accommodates up to 

  two (2) 12AH batteries.

Содержание ACM Series

Страница 1: ...Power Supplies Installation Guide Models Include AL400ULACM 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACM 12VDC or 24VDC 6A Fused Outputs AL1012ULACM 12VDC 10A Fused Outputs AL1024ULACM 24VDC 10A Fus...

Страница 2: ...5A P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACM 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACM 2 6A 5A 250V 1...

Страница 3: ...e no user serviceable parts inside Refer installation and servicing to qualified service personnel 4 Measure voltage before connecting devices This helps avoiding potential damage Input Power input 11...

Страница 4: ...e corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input For non latching hook up Fig 7 pg 9 For la...

Страница 5: ...and reset power to unit BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery i...

Страница 6: ...ctromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Key...

Страница 7: ...non power limited for all other models Battery and AC Supervision Circuit power limited Input power limited Observe polarity Green Flying Lead Unswitched 115VAC power mains non power limited Optional...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...arm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACM Series 11 Notes...

Страница 12: ...re Dimensions 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4...

Отзывы: