Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions, the DC output voltage should be checked for proper 

 

 

voltage level (Output Voltage and Stand-by Specification Charts, pg. 2).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

 

voltage at the battery terminals and at the board terminals marked [+ BAT –] to 

 

 

ensure that there is no break in the battery connection wires.

Note:  AL400ULXB2, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is 0.7A. 

 AL1024ULXB2 

(Power Supply Board) maximum charge current is 3.6A.

Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.

Terminal Identification Tables:

Power Supply Board

Terminal Legend

Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
Do not use G terminal on power supply board (see 

Connect AC, pg. 3).

+ DC –

AL400ULACM - 12VDC @ 4A or 24VDC @ 3A to ACM8 board (power-limited). 
AL600ULACM - 12VDC/24VDC @ 6A to ACM8 board (non power-limited).
AL1012ULACM - 12VDC @ 10A to ACM8 board (non power-limited).
AL1024ULACM - 24VDC @ 10A to ACM8 board (non power-limited).

AC FAIL
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 
AC or brownout fail is reported within 1 minute of event. 
To delay reporting of up to 6 hrs. cut “AC delay” jumper and reset power to unit.

BAT FAIL
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally 
energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery 
is reported within 5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACM), 
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACM).

+ BAT –

Stand-by battery connections. AL400ULXB2, AL600ULXB and AL1012ULXB
(Power Supply Board) maximum charge current is 0.7A. 
AL1024ULXB2 (Power Supply Board) maximum charge current is 3.6A.

ACM8 Access Power Controller

Terminal Legend

Function/Description

– Power +

12VDC or 24VDC input from power supply board.

– C

These terminals can be connected to a separate power-limited UL Listed power supply to 
provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).

TRIGGER INPUT 1 - 
INPUT 8 IN, GND

From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit PIRs, etc.).

OUTPUT 1 -
OUTPUT 8
NC, C, NO, COM

12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO become form “C” 5A 24VAC/VDC rated dry outputs when fuses are 
removed. Contacts shown in a non-triggered state.

FACP INTERFACE
T, + INPUT –

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (Fig. 4 through 8, pgs. 8-9).

FACP INTERFACE
NC, C, NO

Form “C” relay contact rated @ 1A 28VDC for alarm reporting.
(This output has not been evaluated by UL).

Содержание ACM Series

Страница 1: ...Power Supplies Installation Guide Models Include AL400ULACM 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACM 12VDC or 24VDC 6A Fused Outputs AL1012ULACM 12VDC 10A Fused Outputs AL1024ULACM 24VDC 10A Fus...

Страница 2: ...5A P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACM 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACM 2 6A 5A 250V 1...

Страница 3: ...e no user serviceable parts inside Refer installation and servicing to qualified service personnel 4 Measure voltage before connecting devices This helps avoiding potential damage Input Power input 11...

Страница 4: ...e corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input For non latching hook up Fig 7 pg 9 For la...

Страница 5: ...and reset power to unit BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery i...

Страница 6: ...ctromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Key...

Страница 7: ...non power limited for all other models Battery and AC Supervision Circuit power limited Input power limited Observe polarity Green Flying Lead Unswitched 115VAC power mains non power limited Optional...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...arm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACM Series 11 Notes...

Страница 12: ...re Dimensions 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4...

Отзывы: