SPECIAL APPLICATION

400-0384-001

12

7.  

[RDRL]

This command is used to read the status of one 
or all of the internal relays. A ‘1’ indicates the 
relay is on or closed. A ‘0’ indicates the relay is 
off or open. The internal relays have a 
maximum current capacity of 1A and 100VDC.

Command Format: [RDRLnCi]

n

= Relay No. (1, 2, 3, 4 or * for all)

Ci

= Unit ID (i = # from 1 to 99)

Example 1:

The PE1005 has relay number one on (closed) 
and two through four are off. Send the 
command [RDRL*]  to check the status of all 
relays. The feedback will be as follows:

1000

Example 2:

Check the status of relay number one only by 
sending the command [RDRL1]. The feedback 
will be as follows:

1

8.  

[WRRLx

1

x

2

x

3

x

4

]

This command is used to the turn the internal 
relays on or off. A ‘1’ will close the relay, a ‘0’ 
will open a relay and an ‘X’ will leave the status 
of the relay unchanged. The internal relays have 
a maximum current capacity of 1A and 100VDC.

Command Format: [WRRLx

1

x

2

x

3

x

4

Ci]

x

1

= Relay #1

x

2

= Relay #2

x

3

= Relay #3

x

4

= Relay #4

x = 0 for open, or off
x = 1 for closed or on
x = X for no change

Ci

= Unit ID (i = # from 1 to 99)

Example:

Set relay 1 on, relay 4 off, and leave relays 
2 and 3 unchanged. In order to do this, send the 
command [WRRL1XX0]. 

9.  

[WRRLk=x]

This command is used to set one or all internal 
relays on or off. A ‘1’ will close the relay and a 
‘0’ will open a relay. The internal relays have a 
maximum current capacity of 1A and 100VDC.

Command Format: [WRRLk=xCi]

k

= Relay No. (1, 2, 3, 4 or * for all)

x

= Relay Setting (0 = open, 1 = closed)

Ci

= Unit ID (i = # from 1 to 99)

Example:

Set  only  relay 1 on by sending the command 
[WRRL1=1].

10.  

[WRIN]

This command is used to assign  a subroutine 
number to be executed when one of the input 
ports makes a high to low transition. In order to 
create a high to low transition, connect the input 
port to ground using a switch or other contact 
closure device.

Command Format: [WRINn=SUBkCi]

n

= Input No. (1, 2, 3 or 4)

k

= Subroutine(k = # from 1 to 99)

Ci

= Unit ID (i = # from 1 to 99)

Example:

Assign subroutine 10 to be performed when port 
one makes a high to low transition. In order to 
do this, send the command [WRIN1=SUB10]. 
Now, when input port one is shorted to ground, 
subroutine 10 will be executed.

11.  

[RDIN]

This command is used to read the subroutine 
settings for the input ports.

Command Format: [RDINnCi]

n

= Input No. (1, 2, 3, 4 or * for all)

Ci

= Unit ID (i = # from 1 to 99)

Содержание PE1005

Страница 1: ...SPECIAL APPLICATION MANUAL PART NUMBER 400 0384 001 PE1005 CONTROL CARD FOR PIONEER PLASMA DISPLAY USER S GUIDE...

Страница 2: ...NTERNAL VIEW 5 DIAGRAM 3 CARD DETAILS 6 DIAGRAM 4 25 PIN HD DETAILS 7 DIAGRAM 5 MOTION DETECTOR DETAILS 7 INSTALLING YOUR PE1005 8 USB SETUP 8 TCP IP SETUP 8 OPERATION 10 RS 232 CONTROL 10 DESCRIPTION...

Страница 3: ...opping or jarring can damage the card The PE1005 contains components that are sensitive to electro static discharge ESD Always use ESD safety precautions when touching the card 1 5 FCC CE NOTICE This...

Страница 4: ...Wire them in and use them for remote on off brightness up down input select and more Proximity Detector optional An ultrasonic proximity detector allows the execution of any macro based on the proximi...

Страница 5: ...SPECIAL APPLICATION 400 0384 001 4 DESCRIPTION OF PE1005 4 APPLICATION DIAGRAMS 5 DIAGRAM 1 TYPICAL SETUP CONNECTOR RJ 45 NETWORK JACK CONNECTOR TCP IP DIGITAL I O USB 25 PIN D SUB...

Страница 6: ...TX TX TX PDP RX PDP RX VIDEO CARD TX VIDEO CARD EDGE CONNECTOR PE 1005 MAIN MP TX OC OC OC OC INPUT CONTROL 11 12 14 13 ADC DETECTOR MONITOR INPUT REAL TIME RELAY CONTROL 3 4 2 1 CONTACT RELAYS D SUB...

Страница 7: ...0384 001 6 DIAGRAM 3 CARD DETAILS LED1 BATTERY 3V Lithium CR1225 P3 Test Connector Used for circuit card evaluation SW1 RS 232 RS 485 selection The RS 232 position is shown P5 Test Connector Used for...

Страница 8: ...ption PIN Description 1 Input 1 5 Relay 1 Throw 13 GND 21 Motion Det 2 Input 2 6 Relay 1 Pole 14 RS 232 TX 22 Motion Det Trg 3 Input 3 7 Relay 2 Throw 15 GND 23 GND 4 Input 4 8 Relay 2 Pole 16 RS 232...

Страница 9: ...ot connect the PE1005 to the USB port on the computer until after the drivers are installed 3 Check for a readme file that may contain special installation instructions If there is a readme file print...

Страница 10: ...sion This procedure uses the Telnet option Click the Telnet button and do not change the default port number of 9999 9 When the command window appears press ENTER when prompted to enter Setup Mode and...

Страница 11: ...r Commands sent without the unit identifier will be executed by all PE1005 s Example VER Executed by all units VERC1 For Unit ID 1 Only VERC2 For Unit ID 2 Only etc Individual control is accomplished...

Страница 12: ...ed 5 WAIT This command will cause the card to suspend operation for specified period up to ten seconds If several commands are present in a single subroutine use this command to make a pause in betwee...

Страница 13: ...rom 1 to 99 Example Set relay 1 on relay 4 off and leave relays 2 and 3 unchanged In order to do this send the command WRRL1XX0 9 WRRLk x This command is used to set one or all internal relays on or o...

Страница 14: ...s WRRL1 1 WAIT10 WRRL1 0 WAIT10 SET1ALARM30800 and ALRMON1 This is accomplished by sending the following commands WRS10 WRRL1 1 WAIT10 WRRL1 0 1 WRS10 SET1ALARM30800 ALRMON1 0 Now send the command RDS...

Страница 15: ...Unit ID i from 1 to 99 Example Subroutine 50 turns off all the relays and has the label RLYS_OFF Send the command RDS50 and the display will be as follows SUB50 RLYS_OFF WRRL 0 Clear the label for sub...

Страница 16: ...ows DATE 06 01 05 23 RDTIME This command reads back the time from internal clock Command Format RDTIMECi Ci Unit ID i from 1 to 99 Feedback Format hh mm ss Example The current time is 08 40PM Read bac...

Страница 17: ...ine 10 and set Alarm 1 by sending the following commands ALRM1 SUB10 SET1ALRM1 ALRMON1 Alarm 1 is now enabled and running Every second the functions stored in subroutine 10 will be executed 27 SET1ALR...

Страница 18: ...the following commands ALRM1 SUB10 SET1ALRM514300015 ALRMON1 Alarm 1 is now enabled and running Every month on the 15th at 2 30PM the functions stored in subroutine 10 will be executed 31 SET1ALRM6 MO...

Страница 19: ...now enabled and running Every minute when the second count matches 00 the functions stored in subroutine 10 will be executed If the time is 09 59AM the alarm will trigger at the following times 10 00...

Страница 20: ...ing the following commands ALRM2 SUB10 SET2ALRM510003 ALRMON2 Alarm 2 is now enabled and running Every Tuesday at 10 00AM the functions stored in subroutine 10 will be executed ALARM CONTROLS 37 ALRMO...

Страница 21: ...end the hex 0C or form feed character The three characters making up the hex number cannot be separated and must be in the same string Below are some common hex numbers 5B 5D 7B 7D 3C 3E Example Progr...

Страница 22: ...memory location labels Command Format CLRLMkCi k Memory Location m 1 to 99 for all Ci Unit ID i from 1 to 99 Example Clear the contents of all RS 232 memory location labels by sending the command CLR...

Страница 23: ...internal RS 232 port bus to the Video card Command Format OUTVCMmCi m Memory Location m from 1 to 99 Ci Unit ID i from 1 to 99 Example Send the contents of RS memory location 1 to the internal bus to...

Страница 24: ...fined using the SETMD MD0 and MD1 commands Command Format MDONCi Ci Unit ID i from 1 to 99 Example Send the command MDON to activate enable the motion detector 58 MDOFF This command is used to deactiv...

Страница 25: ...ANDS RSI SIDn SIDnCi RSN 63 SIDn This command sets the ID number of all cards connected to the RS 232 bus to the same value The default unit ID is zero Command Format SIDn n New ID n from 1 to 99 Exam...

Страница 26: ...Set Alarm 1 Mode 4 30 SET1ALRM5 Set Alarm 1 Mode 5 31 SET1ALRM6 Set Alarm 1 Mode 6 32 SET2ALRM1 Set Alarm 2 Mode 1 33 SET2ALRM2 Set Alarm 2 Mode 2 34 SET2ALRM3 Set Alarm 2 Mode 3 35 SET2ALRM4 Set Ala...

Страница 27: ...ent mode The plasma may be placed into adjustment mode by sending the command AJY The following examples demonstrate communication with the plasma through the internal bus using both stored commands a...

Страница 28: ...re pins 14 and 16 of the 25 pin HD connector If there is still no response please call Altinex at 714 990 2300 8 2 RELAYS DO NOT WORK Cause 1 Cabling is incorrect Solution See DIAGRAM 4 25 PIN HD DETA...

Страница 29: ...TY RETURN POLICY Please see the Altinex website at www altinex com for details on warranty and return policy 9 2 CONTACT INFORMATION ALTINEX INC 592 Apollo Street Brea CA 92821 USA TEL 714 990 2300 TO...

Отзывы: