Checking the control board fuses, and replacing the board 

 
There are two relays and fuses located in the control board.  These control the compressor and 
electrical heater.  If these are not working, you should check the fuses and relays.  The control board 
may also need replacing. 

1.

 

Firstly, check that the power is turned off to the system.   

2.

 

The white cowling cover will have to be removed from the side of the cylinder to gain access 
to the compressor unit.  This has two screws, one each side. 

3.

 

The controller board is located at the bottom of the compressor unit under a black plastic 
cover, hanging under the right-hand corner of the metal frame that the compressor sits on. 

4.

 

There is one screw at the top centre holding the black plastic cover in place over the 
controller, remove the screw and gently slid the black cover down.  Do not use excessive 
force. 

5.

 

The fuses are located in the two black cylinders.  Use a screwdriver to push, twist and release 
the fuse.  The fuses are 10A, 5x20mm normal blow.  There are are spare fuses taped to the 
inside of the compressor cover. 

6.

 

The main power supply wiring needs to be unscrewed with a screwdriver, but all the other 
connections can be unplugged. 

7.

 

Note that the plugs for the COMP and RES are interchangeable.  The plug with the orange 

and yellow wires goes in the left hand ‘COMP’ port, while the plug with the 

blue and brown 

wires go into the right hand ‘RES’ port.

 

8.

 

There is one screw in the bottom left corner of the board to hold the controller in place. 

9.

 

The controller will then slide out of the backing plate and the new controller fitted. 

10.

 

Don’t forget to fit th

e plug with the ribbon cable for the display. 

 

 

 

Содержание Energie ECO 200esm

Страница 1: ...Solar System Eco Enamel 200esm 250esm 250esms 300esm 300esms Eco Stainless 250i 300i 250is 300is 500is Eco Stainless with coil 250ix 300ix 250isx 300isx 500isx Solar enhanced thermodynamic The smartest way to heat water www taec co nz ...

Страница 2: ...Comply with the requirements of AS NZS 2712 2007 As tested by Applied Research Services P O Box 867 Nelson New Zealand Report number 13 3627 Manual updated July 2020 version 2 5 The Alternative Energy Company Limited 03 540 3003 18 Warren Place Mapua Nelson New Zealand 7005 info taec co nz ...

Страница 3: ...2003 Section 2 The electrical installation of the equipment must comply with the current AS NZ standards and the New Zealand national electrical regulations The electrical input is 240v 50 Hz All hot water pipes must be installed to satisfy the requirements of New Zealand Building Code Clause H1 3 4 except where connected to a heat dissipation device The Eco Thermodynamic Solar System shall only b...

Страница 4: ...stem Operation 11 3 1 Start up of the System 11 3 2 Control panel 12 3 3 Control panel symbols 13 3 4 Keys Functions 13 3 5 Operating Modes 14 3 6 Menu parameters 15 3 7 Parameters Description 16 3 8 Disinfect Function 17 3 9 Holidays Function 17 3 10 PV Function 18 3 11 Table of Errors 19 4 Problem Solving 20 5 System Maintenance 22 5 1 General Inspection 22 5 2 Magnesium Anode 22 5 3 Safety Ther...

Страница 5: ...system cannot be released into the environment Handling of the refrigerant must be carried out by an approved refrigeration technician 1 2 The main components of the system 1 Thermodynamic Solar Panel 2 L shaped brackets for attachment of Aluminum Panel 3 Bolts washer and fixings 6x 4 Copper insulated pair coil pipes 5 Eco hot water cylinder 6 Thermodynamic block 7 Cover with controller display 8 ...

Страница 6: ...772 1172 1315 650 950 1415 370 765 1154 300ix 92 772 1172 1315 650 950 1415 370 765 621 1154 221 500is 92 772 1784 1927 650 950 1990 370 765 1154 500isx 92 772 1784 1927 650 950 1990 370 765 1515 1154 625 1 4 1 5 Solar Panel The Solar Panel is a roll bond type plate manufactured in double channel pressed aluminium with a post press anodization oxidation that creates a dark tone aspect 1 6 Note The...

Страница 7: ...TAEC Eco Owners Manual v2 5 www taec co nz 7 1 7 Technical Features x1 panel ...

Страница 8: ...TAEC Eco Owners Manual v2 5 www taec co nz 8 1 8 Technical Features x2 panels ...

Страница 9: ... well as safety thermostat and temperature probe 1 1 Cover for Eco 2 Condenser Coil 3 One Shot Female Valve 4 One Shot Male Valve 5 Temperature Probe Safety thermostat 6 Electrical element 7 Display 8 External Sheet 9 Magnesium Anode 10 Tank 11 Polyurethane Insulation 12 Adjustable support foot 13 Cold water inlet 14 Recirculation 15 TPR Valve 16 Hot water outlet Note On newer models the anode has...

Страница 10: ...uction number C Serial number D Production date E Volume F Weight G Downstream pressure of PRV H Upstream maximum pressure of PRV I Maximum pressure in hot water cylinder J Maximum temperature in hot water cylinder K Recommended temperature in hot water cylinder C A D B F E H G I J L ...

Страница 11: ...il the controller starts Then follow these instructions Notes When the compressor is started the small C under the ECO will come on and the larger C will start to flash There is a start delay on the compressor will start after a delay the default is 2 minutes The bars on the lower right corner indicate the water temp Note that 4 bars will show at 55 C 5 bars only show when the water is at 65 C dis...

Страница 12: ...e Thermodynamic Solar system Eco is simple and intelligent It allows you to configure several operating parameters according to the operating mode you select It comprises six command keys ON OFF CANCEL MENU COMP E HEATER DISINFECT and OK LOCK which allow you to monitor and change settings ...

Страница 13: ...ally 3 4 Keys Functions KEY FUNCTION DESCRIPTION ON OFF CANCEL ON OFF Switch on off Switch on and off controller CANCEL Exit ESC function to exit menu submenu or cancel settin function OK OK Confirmation Confirm parameters within menus or submenus LOCK Locked Unlocked Lock or unlock keyboard MENU MENU Enter menu COMP ON OFF Compressor Pressing the key allows you to switch on and off the Compressor...

Страница 14: ...t will run as a Thermodynamic System and or electrical heater emersion heater and the operation of the electrical heater is managed in an optimized way to keep the water hot The electrical heater will start every time The user activates it manually key E Heater The contact LP opens low external temperature lack of fluid leak in the circuit etc The compressor running time exceeds parameter T05 The ...

Страница 15: ... Menu parameters Every time it becomes necessary to alter the settings the user must access the Menu The OK key must first be pressed to unlock the system To access the menu the key MENU must be pressed for 3 seconds After accessing use the keys COMP and E HEATER to navigate the menus and submenus In order to confirm values parameters press the key OK LOCK Press the key CANCEL to exit the menu ...

Страница 16: ...P08 Minimum water temperature to activate electrical backup Only visible in Installer level parameter active and configurable only in AUTO 5 OFF 40 ON 16 ON T01 timer Delay time of the compressor 1 20 2 min T05 timer Maximum time the compressor running straight without stopping parameter active and configurable only in AUTO mode 6 OFF 15 ON 12h ON T07 timer Delay time of the compressor after the L...

Страница 17: ...t be nil Automatically when the desired time period is set in the function disinfect The disinfect function is cancelled when you press the CANCEL ON OFF or DISINFECT keys The NZ building code requires the temperature to be raised daily to 60 C daily or weekly to 60 C for one hour It is recommended that the installer sets the disinfect function to weekly with a set point of 65 C 3 9 Holidays Funct...

Страница 18: ...P2 Be careful that this is a dry contact without power Applying power to this contact may cause irreversible damage to the equipment When the contact K1 closes it activates the PV function and all the heat sources both thermodynamic and electric heater will be adjusted to the new working parameters The compressor assumes parameters P01PV H01PV and the electric heater assumes P02PV H02PV Note When ...

Страница 19: ...relay Temperature probes short circuit Measure internal resistance of probe it should be approximately 10 KΩ at the temperature of 25 ºC check that the connector is well attached to the electronic plate and the connection terminals are in good condition LP may not be an error Protectionsystemis activated Check low pressure gauge Check that the connector is properly attached to the electronic plate...

Страница 20: ... circuit breaker ECO mode is selected and outside temperature is very low Alter the equipment to AUTO mode to initiate automatic management of system Alter the equipment to BOOST mode to reheat water faster Error on the display panel Check the presence of error on electronic board and consult the table of errors Have used of large amount of hot water Set the appliance for BOOST mode and wait for w...

Страница 21: ...oblems with the thermodynamic solar system Check the error display in the electronic board Low hot water flow rate Loss or clogging of hot water circuit Check the condition of the hydraulic circuit Loss of water through safety device Absence or incorrect dimensioning of expansion tank if leak is not continuous Installation and or correct dimensioning of expansion tank Pressure in circuit is high i...

Страница 22: ...r does this protecting your tank The wear of the anode always depends on the characteristics of the water you use Checking the condition of the anode is very important particularly in the first few years of the installation so that you will have a good idea of how long it will be before it may need replacing The anode can be located either in the centre at the top of the cylinder or towards the re...

Страница 23: ...the fault has been cured and you intend to reactivate the thermostat please follow this procedure Before checking the switch turn off the power to the system There may be 240v power active at the switch or the electrical element Remove the compressor cover unscrewing the two screws Remove the plastic cover over the electric heater If the small button 2 is protruding the switch has been activated P...

Страница 24: ...top centre holding the black plastic cover in place over the controller remove the screw and gently slid the black cover down Do not use excessive force 5 The fuses are located in the two black cylinders Use a screwdriver to push twist and release the fuse The fuses are 10A 5x20mm normal blow There are are spare fuses taped to the inside of the compressor cover 6 The main power supply wiring needs...

Страница 25: ... erased The equipment should only be installed by qualified installers according to the NZ Standards the NZ Building Code and good trade practises or the instructions of our technical services Further exclusions from guarantee Hot water tanks that have been operating in water with the following indexes Active chlorine 0 2 ppm PH 6 or 8 5 Sorensen scale at 25 C Hardness 3 0 or 20 0 dH 50ppm or 350p...

Страница 26: ...ynamic Hot Water system We are always trying to improve our service and welcome feedback from our valued clients Please contact us at The Alternative Energy Company with your comments The Alternative Energy Company Limited 03 540 3003 18 Warren Place Mapua Nelson New Zealand 7005 info taec co nz ...

Отзывы: