pag. 32
MDE/C133 2561 001
MX3IPG2A
WARNING:
The factory settings may prove not to suit the system. Therefore, the device must be configured anew upon installation
TABELLA DI REGOLAZIONE
tab. C
- FACTORY SETTINGS
DESCRIPTION
FUNCTION
MAIN
ON
OFF
VALUE
rated frequency
fn
50 Hz
direct voltage range
IN_U-
S20
direct rated voltage
Un-
110 V
first underresistance threshold
R<
X
2000 Ohm
starting signalling delay R<
tstart
0 s
trip delay R<
t1
10 s
second underresistance threshold
R<<
X
500 Ohm
starting signalling delay R<<
tstart
0 s
trip delay R<<
t2
3 s
overcurrent threshold
I
~
>
X
0.022 A
starting signalling delay I
~
>
tstart
0 s
trip delay I
~
>
t3
5 s
first dir. undervoltage threshold
U-<
X
0.8 Un
starting signalling delay U-<
tstart
0 s
trip delay U-<
t4
5 s
second dir. undervoltage threshold
U-<<
X
0.7 Un
starting signalling delay U-<<
tstart
0 s
trip delay U-<<
t5
1 s
first dir. overvoltage threshold
U->
X
1.15 Un
starting signalling delay U->>
tstart
0 s
trip delay U->>
t6
5 s
second dir. overvoltage threshold
U->>
X
01.2 Un
starting signalling delay U->>
tstart
0 s
trip delay U->>
t7
1 s
min. pulse width of end relays
t_imp
0.1 s
additional timer
t_X1
1 s
additional timer
t_X2
5 s
additional timer
t_X3
10 s
fault recorder trigger
TRIP
fault recorder pretrigger delay
2 s
SPARE
ON
OFF
VALUE
/
/
/
/
/
/
/
/
/
X
2000 Ohm
0 s
10 s
X
500 Ohm
0 s
3 s
X
0.022 A
0 s
5 s
X
0.8 Un
0 s
5 s
X
0.7 Un
0 s
1 s
X
1.15 Un
0 s
5 s
X
1.2 Un
0 s
1 s
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ not to be allocated: the same settings as the
MAIN ones apply
settings: MAIN
timed LCD backlighting: OFF