pag. 31
MDE/C133 2561 001
MX3IPG2A
tab. B
- TABLE OF SETTINGS
CONTROL MATRIX
DIGITAL
INPUTS
DESCRIPTION
FUNCTION
1
2
3
input enabled by normal de-energizing
first underresistance threshold trip lock
BLOC. R<
sec. underresistance threshold trip lock
BLOC. R<<
overcurrent threshold trip lock
BLOC. I
~
>
overvoltage threshold trip lock
BLOC. U
~
>
undervoltage threshold trip lock
BLOC. U
~
<
first dir. undervolt. threshold trip lock
BLOC.U-<
sec. dir. undervolt. thr. trip lock
BLOC.U-<<
first dir. overvolt. threshold trip lock
BLOC.U->
sec. dir. overvolt. threshold trip lock
BLOC.U->>
timer tX1 start
t_X1
timer tX2 start
t_X2
timer tX3 start
t_X3
switching to spare settings
SETTINGS SWITCH
/
/
reset LED's and output relays
RESET (LED+Xmem)
/
/
X
WARNING:
The factory settings may prove not to suit the system. Therefore, the device must be configured anew upon installation
/ not to be allocated
X allocated