7. Maintenance and Fault Finding
GEM80-500 Series Controller
GEM80-500 Technical Manual (T2025En)
(08/04)
Page 7-12
When the controller is running and the user makes changes to the source version of the
program, the status is displayed on the programming tool as CHANGED instead of
RUNNING until such time as the user recompiles. If the controller is running with status
CHANGED and there is a power interruption, the controller will go into halt mode after
power-up and give a fault report:
"PROGRAM DIFFERENT FROM RUNNING VERSION",
or
"POWER REMOVED WHILE PROGRAM IN A CHANGED STATE".
As part of the self-test procedures which the controller undertakes, there is a check that
there has not been any alteration to program instructions and data in the P-table. Each
time the user makes changes to his program or P-table data, the controller has to
recalculate a CRC value. If power is interrupted before this calculation is complete, the
warning message:
"CRC NOT STORED, PROGRAM MAY HAVE CHANGED"
is displayed on power up, and the controller goes into halt mode. The user may,
however, run the program if desired.
7.10
System Status at Power Up (#500 to #699)
If, during the power-up self-test cycle, one of these fault conditions is detected, the
GEM80-500 Controller will remain in the 'halt' condition and return the fault message
until the fault is cleared. The fault messages are detailed at Table 7-3.
Table 7-3
System Status Error Messages
Code
Fault Message
Possible Causes
Recommended
Recovery
#501 Monitor
Firmware
CRC Test Fail.
Firmware has been corrupted.
Power off/on. If this does
not work the board is
permanently damaged.
#502 System
Firmware
CRC Test Fail.
Firmware has been corrupted.
Power off/on.
Update firmware. If this
does not work the board is
permanently damaged.
#503
No Valid System
Code Found.
Firmware has been corrupted.
Power off/on.
Update firmware. If this
does not work the board is
permanently damaged.
#504 Invalid
Monitor
Mode Selected.
Front Panel Mode Switch in a
Reserved Position.
Correct the Mode Switch
setting.
#505 Workspace
Ram
Test Failed.
Faulty/static damaged RAM
chips.
Power off/on. If this does
not work the board is
permanently damaged.