GEM80-400
4. Communications
Issue 3 04/99
ALSPA GEM 80-400 SERIES CONTROLLERS TECHNICAL MANUAL
Page 4-1
4.
Communications
4.1.
Introduction
GEM
80-400 Controllers may transfer and receive controller memory data using
serial communications links. The serial ports can be used for the following types
of application:
(1)
Operating the GEM 80-400 Controller as part of a distributed controller
network, i.e. data table exchange with other GEM 80 controllers or other
intelligent devices, or supervisory operations or co-ordinated operation of
GEM 80 controllers. Details are given in the 'Data Tables' section
.
(2)
Supplying controller data, i.e. alphanumeric characters for intelligent
devices, printers, VDUs or keyboards, to a computer for statistical analysis
and data logging. See the 'Communication with a Printer, VDU or Suitable
GEM
80 Programming Tool' section for details.
(3)
Connecting the controller to a suitable GEM
80 programming tool, such as
Gemesys 3, or a printer.
(4)
Communication with, and connection to intelligent serial devices and
Central Highway Modules, such as GEMLAN-D and STARNET.
The GEM
80-400 Controller has three serial communications ports, namely Port 1,
Port 2 and Port 3. A 9-way 'D'-type connector is used to connect Ports 1 and 2,
and a 15-way 'D'-type connector is used to connect Port 3; these are situated on
the front panel of the processor module. Port 3 is an RS232/20mA port and is
used to connect either a printer or a suitable GEM
80 programming tool, such as
Gemesys 3, to the controller; it also provides a monitoring facility. Ports 1 and 2
are general purpose RS485/RS232 serial ports which support four different GEM
80
serial communications protocols, these are:
(1)
Extended Simple Protocol (ESP);
(2)
ESP with flexible data tables;
(3)
GEMSTART CCU;
(4)
ASCII (Printer/VDU Terminal).
The signalling rate is user adjustable between 110 and 19,200 bits per second.
These rates are selected by preset data, P-tables, for each port. Figure 4.1
shows the serial port connections.
Содержание GEM80-400 Series
Страница 1: ...GEM80 400 Series Controllers Technical Manual ABCD...
Страница 2: ......
Страница 3: ...ALSPA GEM80 400 Series Controllers Technical Manual Publication No T1614 Issue 3...
Страница 91: ...Page 2 24 ALSPA GEM80 400 SERIES CONTROLLERS TECHNICAL MANUAL Issue 3 04 99 This page left intentionally blank...
Страница 161: ...Page 3 30 ALSPA GEM80 400 SERIES CONTROLLER TECHNICAL MANUAL Issue 3 04 99 Figure 3 13 Typical Module Interlock Circuit...
Страница 170: ...Issue 3 04 99 ALSPA GEM80 400 SERIES CONTROLLER TECHNICAL MANUAL Page 3 39 This page left intentionally blank...
Страница 215: ...Page 5 12 ALSPA GEM80 400 SERIES CONTROLLERS TECHNICAL MANUAL Issue 3 04 99 Figure 5 4 STARNET Module...
Страница 217: ...Page 5 14 ALSPA GEM80 400 SERIES CONTROLLERS TECHNICAL MANUAL Issue 3 04 99 Figure 5 5 GEMLAN D Module...
Страница 252: ...Page 7 16 ALSPA GEM80 400 SERIES CONTROLLERS TECHNICAL MANUAL Issue 3 04 99 This page left intentionally blank...
Страница 273: ...Page 9 6 ALSPA GEM80 400 SERIES CONTROLLERS TECHNICAL MANUAL Issue 3 04 99...
Страница 316: ...Issue 3 04 99 ALSPA GEM80 400 SERIES TECHNICAL MANUAL Page A 5 2 1 1 Cover 2 Base plate Figure A 4 Clamped Cable...