E32.0.93.6C-02 Manual for connection and operation of the JDI-22 page 5 of 10
3.2. Connection data
typical
limitations
between
terminals
min.
max.
min.
max.
notes
Supply voltage
1 and 2
207
V
AC
244
V
AC
0
V
AC
253
V
AC
or corresponding desig-
nation on the type plate
Output 1 (make contact)
3 and 4
253
V
AC
5A
ohmic load
or corresponding desig-
nation on the type plate
Output 2 (change-over
contact)
5, 6 and 7
253
V
AC
10A
ohmic load
or corresponding desig-
nation on the type plate
Input Pt100
10 - 12
0
Ω
∞
Ω
active signal not allowed
Interface
14 and 15
12 V
36 V
0 V
42 V
These limits must not be exceeded (not even for a short time) !
3.3. Connecting an input signal
Please take care not to exceed the limitations of the inputs when connecting the device as this may lead
to destruction of the device:
3.3.1. Connecting a Pt100 RTD probe
Pt100-RTD probe (3-wire)
Pt100-RTD probe (2-wire)
Pt100-RTD probe (4-wire)
3.4. Connecting switching outputs
Hint:
In order to avoid unwanted or wrong switching processes, we suggest to connect the
device’s switching outputs after you have configured the device’s switching outputs
properly.
The device features two switching outputs (relays) by default.
Please take care that you must not exceed the limits of the voltage and of the maximum current
of the switching outputs (not even for a short period of time). Please take extreme care when
switching inductive loads (like coils or relays, etc.). Because of their high voltage peaks, protec-
tive measures (e.g. RC-element) to limit these peaks have to be taken.
Note:
In case of configuring one output as an alarm output, the output will be active in idle state (no
alarm present). The output relay opens when an alarm condition occurred.
3.5. Common wiring of several devices
At the standard devices the power supply, measuring input and the serial interface are electrically isolated of
each other.
At device options (e.g. dc-supply) it can occur that this isolation is not completely guaranteed (e.g. connec-
tion of – power supply to GND).
When interconnecting several of this devices you have to make sure that there is no potential displacement.
Pt100
10
11
12
Pt100
10
11
12
Pt100
10
11
12
set link
non-connected