7. SPECIFICATIONS
7.1 Specifications,
continued
Common Specifications
600, [1000 ]
Input Frequency
60 Hz or 50 Hz (± 3% Hz)
Input Voltage Variation
- 25% to + 10%
Output Frequency
± 0.1 Hz
Output Regulation
± 1% (from 10 - 100% load)
Total Harmonic Distortion
< 5%
Output Waveform
Sine
Step Load Response
< 10% @ 100% load
Noise Attenuation
Common Mode
-120dB (100K - 1 MHz)
Normal Mode
-60dB (100K - 1 MHz)
Low Voltage Trigger
80% nominal voltage (adjustable)
High Voltage Trigger
110% nominal voltage (adjustable)
Batteries
Valve regulated, maintenance-free
Battery Voltage
24 VDC
Batt. Low Volt. Cutout
19.5 VDC (>25% load), [21 VDC (<25% load)]
Charger
Linear (3.5 A max.)
Charger Voltage
27.6 VDC at 25
0
C (adjustable)
Operating Temp
32
0
-104
0
F / 0
0
- 40
0
C
Heat Output
260 BTU, [404 BTU]
Indicators
Line Present, Line Failure,
Low Battery Shutdown,
Low Battery Warning (LED / audible alarm),
Test, Service and Output Load
Controls
Manual Start / Test, Alarm OFF
Connectors
AC Input, AC Output, External Alarm;
Intelligent Interface Device and
External Battery
Output Alarms
Rear panel RJ-45 connector (Form C
contact closures rated 1A, 30 V) for
Line Present / Line Failure, and
Battery OK / Low Battery Warning
Specifications subject to change without notice.