4.3.2.6. Press the scroll up key to execute special functions. The
functions include buzzer ON (as in figure Q1), buzzer OFF (as in figure
Q2, Alarm silence for UPS Warning), and self-test OFF (as in figure R1)
or self-test ON (as in figure R2). The UPS will execute the battery test
for ten seconds.
4.3.3. U
P
S
4.3.3. UPS Default Settings and their alternatives
X
4.3.3.1. Make sure the UPS is not “On”. Press the On
and scroll down
keys simultaneously for approximately three seconds. The
buzzer will sound twice, and the LCD will display figure Q1, indicating
that the UPS is in setting mode.
4.3.3.2. To scroll through the options refer to section
4.3.3.3. Except for Buzzer (figures Q1 and Q2) and Self-test (figures R1 and R2)
all of the other default settings may be changed by pressing the scroll up
key.
4.3.3.4. Figures S1 and S2 indicate the bypass input acceptable window. It
follows the inverter output voltage. Please refer specification for the
detail.
4.3.3.5. Figure T indicates the bypass frequency window of the Inverter Output.
The acceptable setting values are ±3 Hz and ±1 Hz.
4.3.3.6. Figure U indicates the acceptable Inverter Output Voltage. Possible
values are 200, 208, 220, 230, or 240 VAC.
4.3.3.7. Figures V1, V2, V3 and V4 indicate the operation modes of the UPS.
Possible values are Online, Eco (Economical) mode, fixed 50 Hz
Output, and fixed 60 Hz Output.
4.3.3.8. Figure W indicates the adjustment of the Inverter Output, which may be
set to 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
4.3.3.9. After changing settings you must scroll to the “End” screen (figure X)
and then press the enter
key to save all of your changes.
* Press the Enter key to save changes.
4.3.3.10. Turn Off the Utility Input breaker.
4.3.3.11. Your setting changes are now complete.
4.3.3.12. Turn UPS off
(1) Line mode(AC input available) : Press Off key
and hold until
twice beeps heard, UPS output will shut off. UPS will stay in standby
mode, fan(s) keep spinning and battery will be remained recharging if
AC input still available after output is off, otherwise it will be shutdown
completely.
(2) Backup mode (AC input not available): Press Off key
and hold
until twice beeps heard, UPS output will shut off. 10 seconds later, fan
stop spinning and UPS shutdown completely.
4.3.3.13. Self-Test (Line mode only)
The purpose of self-test function is to ensure the backup capability of
battery set, and it can only be applied when UPS is working under line
mode (AC input available) and battery set was proper recharged.
Press
key to change the LCD display to below figure.
And press
key
to start Self-test as below figure