4.3.1.2.  Start-up in Battery Mode (Cold Start) 

This  UPS  can  be  switched  on  without  the  presence  of  an  AC  power 

source. 

Press and hold the ON button ‘

’ until the buzzer beeps. Release 

and then within the next 10 seconds press and hold the same button a 

second  time.  The  UPS  will  perform  its  start-up  procedure.  The  LEDs 

" "  ,"

","

"and  " 

"  will  shine  after  1-5  seconds,  and  the 

buzzer will pulsate to indicate successful power-on. 

Note:  Ensure  that  the  UPS  batteries  are  pre-charged  for  at  least 
four  hours  by  simply  connecting  the  AC  power  cord  to  the  utility 
receptacle. 

4.3.1.3.  Shutdown 

1. Shutdown in AC Mode

Press  and  hold  the  OFF  button  ‘

’  for  five  seconds  until  the

buzzer  beeps.  The  UPS  will  cut  the  power  supply  to  the  outlets.

The  ventilating  fans  will  continue  to  operate.  Switch  off  the  AC

power  source.  The  ventilating  fans  will  stop.  The  UPS  is  now

completely shut down.

2. Shutdown in DC Mode

Press  and  hold  the  OFF  button  ‘

’  for  five  seconds  until  the

buzzer  beeps.  The  UPS  will  cut  the  power  supply  to  the  outlets.

The LEDs will turn off, and the ventilating fans will stop after ten

seconds and the ±BUS discharge is below 42 V. The UPS is now

completely shut down.

4.3.1.4.  Self Testing in AC Mode 

After the UPS has been successfully started in AC mode, press and 

hold  the  Self-Test  button  ‘

 

’  for  five  seconds  until  the  buzzer 

beeps. The          LED  will  shine  to  indicate  that  the  self-test  is  in 

progress. When the  self-test  is  completed the UPS  will  return to AC 

mode. If there were no faults or abnormal conditions then  the LED 
indicators 

and 

LEDs will turn off. 

Note: The main function of self testing is to run a discharge test 
on the batteries. 

Page 

2

0

 to 

47

Page 

2

1

 to 

47

Содержание Continuity 1000

Страница 1: ...Continuity 1000 3000 USER MANUAL...

Страница 2: ...4 4 Installation and Operation 15 4 1 Unpacking 15 4 2 Selecting Installation Position 18 4 3 Operation 19 5 UPS System Block Diagram 33 6 Maintenance Guide 35 6 1 Troubleshooting 35 6 2 Error Codes a...

Страница 3: ...ironments can damage any UPS Install the UPS indoors as it is not designed for installation outdoors 7 To prevent overheating of the UPS keep all ventilation openings free from obstruction and do not...

Страница 4: ...it is not likely to be contacted by people 25 The maximum ambient operating temperature is 40 C o r equivalent 26 Units are considered acceptable for use in a maximum ambient 40 C 27 CAUTION RISK OF...

Страница 5: ...2 2 1 Our High Frequency Transformer less technology and tower convertible enclosure enables the UPS to be integrated into even the most difficult environments with space constraints 2 2 2 This UPS is...

Страница 6: ...voltage for the full load Off indicates abnormal utility voltage 2 In Battery and Load Function Mode indicates battery capacity is 50 Battery Mode LED 1 Indicates load supplied by battery power 2 In B...

Страница 7: ...ack Tower LCD panel Item Sign Description LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within the window 160Vac 288Vac the LED flashes flickeringly to indicat...

Страница 8: ...utput circuit breaker for two outlets 10 AC outlets Program Relay 11 AC outlet Remark Optional function Item Sign Description 1 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at...

Страница 9: ...first 1 EPO ROO input port 2 Optional interface card 3 Optional USB 4 RS 232 3 3 1 True RS 232 The RS 232 interface must be configured as follows Pin Assignments Pin 3 RS 232 Rx Pin 2 RS 232 Tx Pin 5...

Страница 10: ...4 1 1 Installation Instructions Tower installation Rack Mount installation Step 1 Step 2 Step 3 Page 16 to 47 Page 17 to 47...

Страница 11: ...the UPS main power cord into the utility AC power source receptacle 4 Switch on the AC power source All of the LEDs on the front panel display will flash once after five seconds At the same time the...

Страница 12: ...g fans will continue to operate Switch off the AC power source The ventilating fans will stop The UPS is now completely shut down 2 Shutdown in DC Mode Press and hold the OFF button for five seconds u...

Страница 13: ...n you see figure B means the starting up procedure is finished Please ensure UPS recharge in line mode for at least 4 hours for fully recharged before the first backup test if it s a new installed uni...

Страница 14: ...y 1 UPS measurements can be checked after UPS started by pressing select key The display sequence are as below figure F AC input voltage figure G AC input frequency figure H UPS output voltage figure...

Страница 15: ...eard d Unplug AC input power cord or turn off power source switch e After UPS completely shut off UPS is unlocked 4 3 2 5 UPS Default Data and Special Function Execution After the UPS completely start...

Страница 16: ...is 3 Hz U inverter output voltage V1 The UPS is operating in normal mode V2 The UPS is operating in Eco mode V3 The UPS is operating in CVCF 50 Hz mode V4 The UPS is operating in CVCF 60 Hz mode W Out...

Страница 17: ...3 3 7 Figures V1 V2 V3 and V4 indicate the operation modes of the UPS Possible values are Online Eco Economical mode fixed 50 Hz Output and fixed 60 Hz Output 4 3 3 8 Figure W indicates the adjustmen...

Страница 18: ...ce per second Battery low Quick and short successive beeps Confirm RS 232 port receiving two quick and short beeps Service mode okay one quick and short beep 5 UPS System Block Diagram Figure 4 1 Figu...

Страница 19: ...11 UPS Over Temperature 3 Remove any objects obstructing the ventilation louvers Verify that the cooling fans are working properly Contact your local dealer to replace the fans if necessary 4 Site wir...

Страница 20: ...ches back and forth between battery and utility modes 1 A power strip is connected to the UPS See if there is any damage to the utility wall receptacle or if the cord plug is faulty 1 Do not use the p...

Страница 21: ...saved your data in any open computer applications before you proceed with this battery test Code Meaning Er05 Battery weak or faulty Er06 Output short circuited Er07 EPO mode Er11 UPS over temperatur...

Страница 22: ...contact 4 Inverter On 5 Battery Low 6 Battery Bad or Abnormal 7 UPS Alarm 8 Common 9 Shutdown UPS positive signal 10 Shutdown UPS negative signal 8 3 2 8 3 3 8 3 4 8 3 5 8 3 6 The shutdown function wi...

Страница 23: ...0 9 900 1800 2700W INPUT Voltage Rating 110 150 180 300 VAC Based on load percentage0 60 0 75 0 100 Frequency Rating 45 65 Hz Phase Single phase with ground Power Factor 0 99 with full linear load Ge...

Страница 24: ...cy Full Linear Load Line mode Rating 230Vac 90 91 91 Battery mode 12Vdc pcs 86 87 87 ECO mode Rating 230Vac 97 97 97 MODEL ITEM CONTINUITY PLUS 1K CONTINUITY PLUS 2K CONTINUITY PLUS 3K Battery Sealed...

Страница 25: ...ctronic Circuit Battery ABDM EPO UPS shuts down immediately Over Temperature Normal Mode Transfer to Bypass Mode Battery Mode UPS shuts down immediately Physical Dimensions UPS inches W x H x D mm 17...

Страница 26: ...k energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Alpha and Outback Energ...

Отзывы: