Subject to change without notice | 83024000bUK – Translation of the original operating manual | ait-deutschland GmbH
Lift panels off the packing unit 2 and set them
down
If the unit is not transported by a lift truck: Do not lift
the unit off the pallet until the panel packages (
“5.1
Scope of supply“, page 8, pos. 2, 3 and 6) have
been unpacked and lifted off the pallet.
Optional separation of the fan module
NOTE
If required (tight passages), the fan module
can be removed.
1. Disconnect the plug connections of the load and
bus cables at the top left on the switch box of the
cooling circuit for the fan module.
2. Remove the 4 screws from the fan module.
3. Remove the fan module and set it down safely.
4.
Break off the protruding links on the polystyrene
cross-pieces.
1 Tensioning straps with openings for carrying
2 Polystyrene links
3 Screws on the fan module
Carrying the unit, transport using handcart
The housing panels have been set down.
There are two circumferential tensioning straps on the
heat pump module with openings at different heights
that can be used for lifting and carrying.
Two support crosspieces are clamped into the recess-
es at the sides for the air ducts for stability – do not re-
move them both until after transport.
Transport of the heat pump module with
a handcart
1. Only load the heat pump module on to the hand-
cart with the narrow side, left or right.
2. Secure the heat pump module on the handcart
with a tensioning strap.
3. Transport the heat pump module to the installa-
tion site.
5.4 Installation
CAUTION!
In the air outlet area, the air temperature is
approx. 5 K below the ambient temperature.
Under certain climatic conditions an ice lay-
er can therefore develop in the air outlet area.
Install the heat pump so that the air blower
does not discharge into footpath areas.
NOTE
Always comply with the installation plan for
the respective model. Note the size and mini-
mum clearances.
Installation plan for the respective model, from
Page 24