![Alpha ESS SMILE-G3-B5 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/alpha-ess/smile-g3-b5/smile-g3-b5_manual_2905573048.webp)
49
ELECTRICAL CONNECTION
3)
Take out 10 pin terminal block for AUX connection.
AUX contains Channel1 and Channel2.Channel1 contains Do1_NO (normally open), Do1_COM
and Do1_NC (normally closed), corresponding to 1, 2 and 3 respectively. Channel2 contains
Do2_NO, Do2_COM and Do2_NC, corresponding to 4, 5 and 6 respectively.
Channel 1
1
Do1_NO
2
Do1_COM
3
Do1_NC
Channel 2
4
Do2_NO
5
Do2_COM
6
Do2_NC
If using a generator unit with dry contact, the dry contact can be wired to 1 (Do1_NO) and 2
(Do1_COM) of Channel 1 as shown in the diagram below. If using a generator unit without
dry contact, no wiring is required.
2.
Place the COM connection cover against the inverter and tighten them.