Alpes Technologies ALPTEC 3.2 Скачать руководство пользователя страница 9

9

Parameter table (continued)

Cod

Description

ACC

UoM

DEF

RANGE

P.37

Fan start temperature

Adv

°

55

0 .. 100°C

(32...212°F)

P.38

Fan stop temperature

Adv

°

50

0 .. 100°C

(32...212°F)

P.39

Temperature alarm threshold

Adv

°

45

50 .. 100°C

(122...212°F)

P.40

Step failure alarm threshold

Adv

%

75

OFF / 25…100

P.41

Maximum voltage alarm threshold

(1)

Adv

%

N.A.

OFF / 90...150

P.42

Minimum voltage alarm threshold

(1)

Adv

%

N.A.

OFF / 60..110

P.43

THD V alarm threshold

(1)

Adv

%

N.A.

OFF / 5..250

P.44

THD I alarm threshold

(1)

Adv

%

N.A.

OFF / 5..250

P.45

Maintenance interval

Adv

h

4380

1 - 30000

P.46

Bar-graph function

Usr

Kvar ins/

tot

Kvar ins/tot

Corr att/nom

Delta kvar att/tot

P.47

Default auxiliary measure

Usr

V

Deltakvar

V

A

WeekPF

Overload

Temp

THDV

THDI

ROT

P.48

Backlight flashing on alarm

Usr

ON

OFF

ON

P.49

Serial node address

Usr

01

01-255

P.50

Serial speed

Usr

bps

9.6k

1.2k

2.4k

4.8k

9.6k

19.2k

38.4k

P.51

Data format

Usr

8 bit – n

8 bit, sans parité

8 bit, impair

8bit, pair

7 bit, impair

7 bit, pair

P.52

Stop bits

Usr

1

1-2

P.53

Protocol

Usr

Modbus

RTU

Modbus RTU

Modbus ASCII

(1) Any modification of these parameters without written authorisation from Alpes excludes all warranty for the equipments

P.21

– If set to OFF, password management is disabled and anyone has access to the settings and commands menu.

P.22

– With P.21 enabled, this is the value to specify for activating user level access. See Password access chapter.

P.23

– As for P.22, with reference to Advanced level access

P.24

– Number of phases of the power correction panel.

P.25

- Enables the measurement of the actual power of the step, performed each time they are switched in. The measure is calculated, as the current

measurement is referred to the whole load of the plant. The measured power of the steps is adjusted (trimmed) after each switching and is displayed on

the step life statistic page.

P.26 – P.27

- Tolerance around the setpoint. When the cosphi is within the range delimited by these parameters, in AUT mode the device does not connect /

disconnect steps even if the delta-kvar is greater than the smallest step.

P.28

- Selecting mode of steps insertion.

Standard mode

- Normal operation with free selection of the steps

Linear mode

- the steps are connected in progression from left towards right only following the step number and according to the LIFO (Last In First

Out) logic. The controller will not connect a step when the system steps are of different ratings and by connecting the next step, the set-point value

would be exceeded.

P.29

- Setpoint used when the system is generating active power to the supplier (with negative active power / power factor ).

P.30

- Disconnection sensitivity. Same as the previous parameter but related to disconnection. If set to OFF the disconnection has the same reaction time of

connection set with the previous parameter.

P.31

- If set to ON, when switching from AUT mode to MAN mode, steps are disconnected in sequence.

P.32

– Trip threshold for the capacitors overload protection (alarm A08), that will arise after a integral delay time, inversely proportional to the value of the

overload.

2014-AT3-5-01-ANG.indd 9

20/03/14 11:46

Содержание ALPTEC 3.2

Страница 1: ...stalled by qualified personnel complying to current standards to avoid damages or safety hazards Before any maintenance operation on the device remove all the voltages from measuring and supply inputs...

Страница 2: ...ble 2 level password protection for settings Backup copy of original commissioning settings Built in temperature sensor Tool less panel mount Display indications Introduction The ALPTEC automatic powe...

Страница 3: ...en when the power supply voltage is removed When the power returns the original state of the steps is restored Select step Change step status MAN mode icon Connected steps Tot kvar inserited in MAN Ma...

Страница 4: ...stortion THD of plant voltage VH02 VH1 5 voltage harmonic content from 2 nd up to 15 th order Current THD THDI Total harmonic distortion THD of plant current IH02 IH15 Current harmonic content from 2...

Страница 5: ...ured through the front optical port using the IR USB code CX01 programming dongle or with the IR WiFi code CX02 dongle This programming port has the following advantages You can configure and service...

Страница 6: ...tom menu non available on this version EXIT Exits without saving cancel SAVE Exits saving modifications Press MAN AUT to access the submenu When you are in a submenu the main display shows the code of...

Страница 7: ...acters available The parameter code can be used however as a reference Note The parameters shown in the table with a shaded background are essential to the operation of the system thus they represent...

Страница 8: ...With small values of P 10 the regulation is fast more accurate around the setpoint but with more step swithchings With high values instead we ll have slower reactions of the regulation with fewer swit...

Страница 9: ...vanced level access P 24 Number of phases of the power correction panel P 25 Enables the measurement of the actual power of the step performed each time they are switched in The measure is calculated...

Страница 10: ...ctually inserted with reference to the total reactive power installed in the panel Curr act nom Percentage of actual plant current with reference to the maximum current of the CT Delta kvar bar graph...

Страница 11: ...rm activation A12 Adv ALA OFF ON ALA DISC A D P 95 Alarm delay A12 Adv 0 0 240 P 96 Delay UoM A12 Adv Sec Min Sec P 97 Alarm activation A13 Adv A D OFF ON ALA DISC A D P 98 Alarm delay A13 Adv 5 0 240...

Страница 12: ...er than minimum measuring range The plent should be off load A04 Current too high The current flowing in the current inputs is higher than maximum measuring range A05 Voltage too low The measured volt...

Страница 13: ...o execute the selected command The unit will prompt for a confirmation OK Press once again MAN AUT to confirm or MODE to cancel The following table lists the possible commands COD COMMAND DESCRIPTION...

Страница 14: ...N P 24 1PH NOTES IMPORTANT The polarity of the current voltage input is indifferent Configuration with MV measurement and correction on LV side Typical diagram do not represent the internal connexion...

Страница 15: ...rrent Ie 1 AA or 5 AA Measuring range for 5A scale 0 025 6AA for 1A scale 0 025 1 2AA Type of input Shunt supplied by an External current transformer low voltage Max 5A Measuring method True RMS Overl...

Страница 16: ...0 56 Nm 5 LBin Housing Version Flush mount Material Polycarbonate Degree of protection IP54 on front IP20 terminals Weight 350g Certifications and compliance cULus Pending Reference standards IEC EN...

Отзывы: