Alpes Technologies ALPTEC 3.2 Скачать руководство пользователя страница 12

12

Commands menu

– The commands menu allows executing some occasional operations like reading peaks resetting, counters clearing, alarms reset, etc.

– If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration.

– The following table lists the functions available in the commands menu, divided by the access level required.

– With controller in MAN mode, press the MODE button for 5 seconds.

– Press

to select CMD.

– Press MAN-AUT to access the Commands menu.

– Select the desired command with MODE or MAN-AUT.

– Press and hold for three seconds

if you want to execute the selected command. ALPTEC shows OK? with a countdown.

– If you press and hold

until the end of the countdown the command is executed, while if you release the key before the end, the command is canceled.

COD

COMMAND

PWD.

ACCESS LEVEL

DESCRIPTION

C01

RESET MAINTENANCE

Adv

Reset maintenance service interval.

C02

RESET STEP COUNT

Adv

Reset step operation counters.

C03

RESET STEP TRIMMING

Adv

Reload originally programmed power into step trimming.

C04

RESET STEP HOURS

Adv

Reset step operation hour meters.

C05

RESET MAx VALUES

Adv

Reset maximum peak values.

C06

RESET WEEKLY TPF

Adv

Resets weekly total power factor history.

C07

SETUP TO DEFAULT

Adv

Resets setup programming to factory default.

C08

SETUP BACKUP

Adv

Makes a backup copy of user’s setup parameters settings.

C09

SETUP RESTORE

Adv

Reloads setup parameters with the backup of user settings.

Alarm description

COD

ALARM

DESCRIPTION

A01

Undercompensation

All the available steps are connected but the cosphi is still more inductive than the setpoint.

A02

Overcompensation

All the steps are disconnected but the cosphi is still more capacitive than the setpoint.

A03

Current too low

The current flowing in the current inputs is lower than minimum measuring range. The plent should be

off-load.

A04

Current too high

The current flowing in the current inputs is higher than maximum measuring range.

A05

Voltage too low

The measured voltage is lower than the threshold set with P.42.

A06

Voltage too high

The measured voltage is higher than the threshold set with P.41.

A07

Panel temperature too high

The panel temperature is higher than threshold set with P.39.

A08

Capacitor current overload

The calculated capacitor current overload is higher than threshold set with P.32 and P.33.

A09

No-Voltage release

A no-voltage release has occoured on the line voltage inputs, lasting more than 8ms.

A10

Voltage THD too high

The THD of the plant voltage is higher than the threshold set with P.43.

A11

Current THD too high

The THD of the plant current is higher than the threshold set with P.44.

A12

Maintenance requested

The maintenance interval set with P.45 has elapsed. To reset the alarm use the command C.xx (see

Command menu)

A13

Step failure

The residual power of step xx is lower than minimum threshold set with P.40.

COD

DESCRIPTION

ENAbLE

ALARM RELAy

DISCONNECTION

DELAy

A01

Undercompensation

15 min

A02

Overcompensation

120 s

A03

Current too low

5 s

A04

Current too high

120 s

A05

Voltage too low

0 s

A06

Voltage too high

0 s

A07

Capacitor current overload

30 s

A08

Temperature too high

60 s

A09

No-Voltage release

0 s

A10

Voltage THD too high

5 s

A11

Current THD too high

5 s

A12

Maintenance requested

0 s

A13

Step failure

5 s

Alarms

– When an alarm is generated, the display will show an alarm icon, the code and the description of the alarm in the language selected.

– If the navigation keys in the pages are pressed, the scrolling message showing the alarm indications will disappear momentarily, to reappear again after a

few seconds.

– Alarms are automatically resetted as soon as the alarm conditions that have generated them disappear.

– In the case of one or more alarms, the behaviour of the ALPTEC depends on the properties settings of the active alarms.

2014-AT3-5-01-ANG.indd 12

20/03/14 11:46

Содержание ALPTEC 3.2

Страница 1: ...stalled by qualified personnel complying to current standards to avoid damages or safety hazards Before any maintenance operation on the device remove all the voltages from measuring and supply inputs...

Страница 2: ...ble 2 level password protection for settings Backup copy of original commissioning settings Built in temperature sensor Tool less panel mount Display indications Introduction The ALPTEC automatic powe...

Страница 3: ...en when the power supply voltage is removed When the power returns the original state of the steps is restored Select step Change step status MAN mode icon Connected steps Tot kvar inserited in MAN Ma...

Страница 4: ...stortion THD of plant voltage VH02 VH1 5 voltage harmonic content from 2 nd up to 15 th order Current THD THDI Total harmonic distortion THD of plant current IH02 IH15 Current harmonic content from 2...

Страница 5: ...ured through the front optical port using the IR USB code CX01 programming dongle or with the IR WiFi code CX02 dongle This programming port has the following advantages You can configure and service...

Страница 6: ...tom menu non available on this version EXIT Exits without saving cancel SAVE Exits saving modifications Press MAN AUT to access the submenu When you are in a submenu the main display shows the code of...

Страница 7: ...acters available The parameter code can be used however as a reference Note The parameters shown in the table with a shaded background are essential to the operation of the system thus they represent...

Страница 8: ...With small values of P 10 the regulation is fast more accurate around the setpoint but with more step swithchings With high values instead we ll have slower reactions of the regulation with fewer swit...

Страница 9: ...vanced level access P 24 Number of phases of the power correction panel P 25 Enables the measurement of the actual power of the step performed each time they are switched in The measure is calculated...

Страница 10: ...ctually inserted with reference to the total reactive power installed in the panel Curr act nom Percentage of actual plant current with reference to the maximum current of the CT Delta kvar bar graph...

Страница 11: ...rm activation A12 Adv ALA OFF ON ALA DISC A D P 95 Alarm delay A12 Adv 0 0 240 P 96 Delay UoM A12 Adv Sec Min Sec P 97 Alarm activation A13 Adv A D OFF ON ALA DISC A D P 98 Alarm delay A13 Adv 5 0 240...

Страница 12: ...er than minimum measuring range The plent should be off load A04 Current too high The current flowing in the current inputs is higher than maximum measuring range A05 Voltage too low The measured volt...

Страница 13: ...o execute the selected command The unit will prompt for a confirmation OK Press once again MAN AUT to confirm or MODE to cancel The following table lists the possible commands COD COMMAND DESCRIPTION...

Страница 14: ...N P 24 1PH NOTES IMPORTANT The polarity of the current voltage input is indifferent Configuration with MV measurement and correction on LV side Typical diagram do not represent the internal connexion...

Страница 15: ...rrent Ie 1 AA or 5 AA Measuring range for 5A scale 0 025 6AA for 1A scale 0 025 1 2AA Type of input Shunt supplied by an External current transformer low voltage Max 5A Measuring method True RMS Overl...

Страница 16: ...0 56 Nm 5 LBin Housing Version Flush mount Material Polycarbonate Degree of protection IP54 on front IP20 terminals Weight 350g Certifications and compliance cULus Pending Reference standards IEC EN...

Отзывы: