Rapid CT set-up

– When the CT value is not known and only used at the moment of the installation, the P.01 parameter for CT primary can remain set at OFF while all the others

can be programmed.

– In this case, during the system installation and once the controller is powered up, the display will show a flashing CT (Current Transformer). By pressing

▲ ▼

the CT primary can be set directly.

Once programmed, press MAN/AUT to confirm. The unit will store the setting into P.01, and directly restart in automatic mode

Parameter table

– Below are listed all the programming parameters in tabular form. For each parameter are indicated the possible setting range and factory default, as well

as a brief explanation of the function of the parameter. The description of the parameter shown on the display can in some cases be different from what is

reported in the table because of the reduced number of characters available. The parameter code can be used however as a reference.

Note: The parameters shown in the table with a shaded background are essential to the operation of the system, thus they represent the minimum

programming required for operation.

BASE MENU

Cod

Description

ACC

UoM

DEF

RANGE

P.01

CT primary

Usr

A

OFF

OFF / 1...10.000

P.02

CT secondary

Usr

A

5

1 / 5

P.03

CT read phase

Usr

L1

L1

L2

L3

P.04

CT wiring polarity

Usr

Aut

Aut

Dir

Rev

P.05

Voltage read phase

Usr

L2-L3

L1-L2

L2-L3

L3-L1

L1-N

L2-N

L3-N

P.06

Smallest step power

Usr

Kvar

1.00

0.10 ... 10000

P.07

Rated capacitor voltage

Usr

V

410V

50 ... 50000

P.08

Nominal frequency

Usr

Hz

Aut

Aut

50Hz
60Hz

Var

P.09

Reconnection time

Adv

s

180

1 … 30000

P.10

Sensitivity

Usr

s

30

1 … 1000

P.11

Step 1 function

Usr

OFF

OFF

1…32

ON

NOA

NCA

FAN

A01…A13

P.12

Step 2 function

Usr

OFF

=

P.13

Step 3 function

Usr

OFF

=

P.14

Step 4 function

Usr

OFF

=

P.15

Step 5 function

Usr

OFF

=

P.16

Step 6 function

Usr

OFF

=

P.17

Step 7 function

Usr

OFF

=

P.19

Cos-phi setpoint

Usr

0.96

IND

0.50 Ind – 0.50 Cap

P.20

Alarm messages language

Usr

ENG

ENG

ITA

FRA

SPA

POR

DEU

2014-AT3-5-01-ANG.indd 7

20/03/14 11:46

Содержание ALPTEC 3.2

Страница 1: ...stalled by qualified personnel complying to current standards to avoid damages or safety hazards Before any maintenance operation on the device remove all the voltages from measuring and supply inputs...

Страница 2: ...ble 2 level password protection for settings Backup copy of original commissioning settings Built in temperature sensor Tool less panel mount Display indications Introduction The ALPTEC automatic powe...

Страница 3: ...en when the power supply voltage is removed When the power returns the original state of the steps is restored Select step Change step status MAN mode icon Connected steps Tot kvar inserited in MAN Ma...

Страница 4: ...stortion THD of plant voltage VH02 VH1 5 voltage harmonic content from 2 nd up to 15 th order Current THD THDI Total harmonic distortion THD of plant current IH02 IH15 Current harmonic content from 2...

Страница 5: ...ured through the front optical port using the IR USB code CX01 programming dongle or with the IR WiFi code CX02 dongle This programming port has the following advantages You can configure and service...

Страница 6: ...tom menu non available on this version EXIT Exits without saving cancel SAVE Exits saving modifications Press MAN AUT to access the submenu When you are in a submenu the main display shows the code of...

Страница 7: ...acters available The parameter code can be used however as a reference Note The parameters shown in the table with a shaded background are essential to the operation of the system thus they represent...

Страница 8: ...With small values of P 10 the regulation is fast more accurate around the setpoint but with more step swithchings With high values instead we ll have slower reactions of the regulation with fewer swit...

Страница 9: ...vanced level access P 24 Number of phases of the power correction panel P 25 Enables the measurement of the actual power of the step performed each time they are switched in The measure is calculated...

Страница 10: ...ctually inserted with reference to the total reactive power installed in the panel Curr act nom Percentage of actual plant current with reference to the maximum current of the CT Delta kvar bar graph...

Страница 11: ...rm activation A12 Adv ALA OFF ON ALA DISC A D P 95 Alarm delay A12 Adv 0 0 240 P 96 Delay UoM A12 Adv Sec Min Sec P 97 Alarm activation A13 Adv A D OFF ON ALA DISC A D P 98 Alarm delay A13 Adv 5 0 240...

Страница 12: ...er than minimum measuring range The plent should be off load A04 Current too high The current flowing in the current inputs is higher than maximum measuring range A05 Voltage too low The measured volt...

Страница 13: ...o execute the selected command The unit will prompt for a confirmation OK Press once again MAN AUT to confirm or MODE to cancel The following table lists the possible commands COD COMMAND DESCRIPTION...

Страница 14: ...N P 24 1PH NOTES IMPORTANT The polarity of the current voltage input is indifferent Configuration with MV measurement and correction on LV side Typical diagram do not represent the internal connexion...

Страница 15: ...rrent Ie 1 AA or 5 AA Measuring range for 5A scale 0 025 6AA for 1A scale 0 025 1 2AA Type of input Shunt supplied by an External current transformer low voltage Max 5A Measuring method True RMS Overl...

Страница 16: ...0 56 Nm 5 LBin Housing Version Flush mount Material Polycarbonate Degree of protection IP54 on front IP20 terminals Weight 350g Certifications and compliance cULus Pending Reference standards IEC EN...

Отзывы: