6.1.1 Access door
For opening the device, pull the door on the upper part.
6.1.2 Washing the filters
Filter maintenance is important both for the correct operation of the device and for constant performance
over time. The following materials are required for maintenance:
1. Two plastic trays, one with the bottom raised 2-3 cm for decanting the dirt. As an alternative to the raised
bottom, use a stainless steel frame.
2. Non-corrosive detergent for washing the electrostatic cells, supplied by an authorised dealer.
3. A rubber tube for rinsing the filters.
Prepare the tray with the raised bottom with warm water (max 45°C). Dilute the detergent in the proportions
indicated on the label of the detergent itself.
15
6
O R D I N A R Y M A I N T E N A N C E
Ordinary maintenance involves:
-
maintenance of the filter unit
-
general inspection of the machine
Extraordinary maintenance is carried out by specialised personnel.
6 . 1
F I L T E R M A I N T E N A N C E
To carry out filter maintenance, it is necessary to gain access to them through the provided door and
consists in washing the filter cell and the metal pre-filter
6 . 1 . 1
A c c e s s D o o r
For opening the machine, pull the door on the upper part.
To open the access door, it is necessary to
release the two locks with a flat screwdriver
and remove the door.
To open the access door,
it is necessary to release
the two locks with a flat
screwdriver and remove
the door.
16
6 . 1 . 2
W a s h i n g t h e f i l t e r s
Filter maintenance is important both for the correct operation of the machine and for constant performance
with the passage of time. The following materials are required for maintenance:
1) Two plastic trays, one with the bottom raised 2-3 cm for decanting the dirt. As an alternative to the raised
bottom, use a stainless steel frame.
2) Non-corrosive detergent for washing the electrostatic cells, supplied by an authorised dealer.
3) A rubber tube for rinsing the filters.
4) Vinegar.
Prepare the tray with the raised bottom with warm water (max 45°C). Dilute the detergent in the proportions
indicated on the label of the detergent itself.
Put the vinegar and water in the other (1 litre of vinegar for every 20 litres of water).
water and detergent
tray in plastic or stainless steel
electrostatic cell
frame in plastic or stainless steel
To wash, proceed as follows:
a) immerse the electrostatic cell in the tray with the detergent and leave to soak for 5÷10minutes
b) remove the electrostatic cell and rinse thoroughly with running water, taking care not to break the
ionisation wires
rinsing with current water
drying
water and detergent
tray in plastic or stainless steel
electrostatic cell
frame in plastic or stainless steel
c
ALNOR
®
ventilation systems
is a legally protected trademark and technical patent. All rights reserved.
26
w
w
w
.al
nor
.c
om.
pl
User’s manual
e-MOCarz