EP10A

 compact blower

 

e. Electrical connections

 

Units are typically driven by a metric frame electric motor with an environmental protection level IP55. If alternative 

 

motors are supplied, reference to the motor rating plate is required for all electrical details. The blower is designed to be 

 

continuously run at its designated speed, any inverter drive program giving speed control and/ or speed changes must be 

 

approved by Almeco. 

 

 

If a star/ delta starter has not been supplied with the unit, it is not Almeco’s responsibility to control the starting of the 

 unit.

 

 

I.  We recommend that a soft start with thermistor control is used to start the blower, or an inverter with ramp-up 

 

 

and down time set at 5 seconds.

 

II.  If star/delta starting is used and switched by a plc, it is the customer’s responsibility to ensure that the switching 

 

 

times are correct. In this case the number of start/stops is limited to 6 per hour.

 

III.  All wiring should be installed to national wiring standards.

 

 

Table 1: Motor configuration options:

a. Delta configuration

b. Star configuration

c. Star/ delta starter
If an inverter is not used, use a suitable 

starter with overload protection star/ 

delta starter.

 

f. Shaft rotation 

 All units rotate counter clockwise when viewing the blower from the cooling fan of the motor. Alternatively, clockwise 

 when viewing the polley/ shaft end.

 NOTE (a): Air will flow out of the blower discharge even when it is run in reverse but at approximately 60% of the normal 

 performance.

 NOTE (b): 

• 

Never run the blower unit without the belt and belt guard fitted.

• 

Never run the blower when disconnected from ducting/ air delivery device.

• 

Always ensure that the power is isolated and locked off before commencing any maintenance on the unit.

• 

Before operating the blower ensure that the blower is secured in position.

  

All blower motors are supplied with a thermistor connection. It is important to use these as it protects the motor and 

may prevent the motor/blower from failure. All Almeco starters provide this safety cut-out feature. As an optional extra 

the blower head can come equipped with two thermal cut-out probes which provide the blower head bearings with 

additional protection. These probes will be pre-wired into the motor thermistor circuit and are wired into terminals T1 and 

T2 as shown in Figure 4.

!

!

Ramp-up and down times should be set at no less than 5 seconds.

Incorrect fan rotation is the most common cause of drying system under 

performance. Double check!

Содержание ACI EP10A

Страница 1: ...www almeco eu DRYING SYSTEMS EP10A Compact blower Installation operation maintenance Instruction manual EP10A compact blower...

Страница 2: ...information 4 a Description and model identification b Equipment arrival 3 Key features and dimensions 5 a Key EP10A features b Key EP10AH features c Illustration further EP10A key features 4 Install...

Страница 3: ...of starts and stops if so then use a timer delay in the control to avoid frequent switching The EP10A blower needs to have airflow passing through it to ensure temperatures are not exceeded The use of...

Страница 4: ...or as a hot air version EP10AH where air temperatures of up to 365 F 185 C can be processed Almeco clearly labels each EP10A EP10AH blower unit on the back of the blower head as well as the motor cow...

Страница 5: ...er should be cleaned regularly and the main element replaced every six months Drive belt guard Poly V belt Motor pulley Motor IE3 Blowerhead EP10 A Filter Ref B3 003 039 B3 000 185 Pre lter B3 000 147...

Страница 6: ...www almeco eu Ref B3 003 037 Thermal cut Hot air Ref ACEP 250H 7 EP10A compact blower c Illustration furtherEP10AKeyFeatures d EP10AHeadOptions Electric Motor Standard Metric or NEMA Filter Assembly B...

Страница 7: ...mounting plate is provided to suit the large C face configuration NOTE Allow room for bracket movement during belt replacement Very low vibration levels of these units allow them to be bolted to any...

Страница 8: ...r If an inverter is not used use a suitable starter with overload protection star delta starter f Shaft rotation All units rotate counter clockwise when viewing the blower from the cooling fan of the...

Страница 9: ...tend the life of the mechanical components and ensure continued efficiency and longevity Removing filter element Step 1 Remove pre filter element by releasing the security nut and washer Use a 17mm AF...

Страница 10: ...f the unit is still not dry Re fitting filter elements Once the main filter element and the pre filter sock are thoroughly dried they can be re fitted to each other Refit the filter and its cover and...

Страница 11: ...2 nuts on the adjusting screw apply sufficient tension to raise the blower head back plate assembly into its approximate position and lightly tighten the M10 bolts to hold the assembly in place Tensio...

Страница 12: ...ith the poly vee pulleys Do not force the belt or roll the belt onto the pulleys Ensure the blower head is low enough to allow the belt to clear before attempting to fit Using the M12 nuts on the adju...

Страница 13: ...lter Maintenance Damaged hose lining Replace damaged hose Air leaks in system Check replace damaged hose and clips Drive belt slipping Worn Pulley Replace transmission parts Incorrect speed from contr...

Страница 14: ...cal overloading Exceeding rated CFM Reduce open area of air delivery devices i e slot width of Airknives Blower not piped to system Only run blower when connected to the operating system Never run in...

Страница 15: ...espective manufacturer s policy Motors and other items for which a national service network is in place should be sent directly to that manufacturer s representative for the most prompt service Almeco...