OUTDOOR UNIT
CONNECTS TO
(2) RAST 6-PIN
CONNECTORS
LOW VOLTAGE
MAKE-UP BOX
ROUTE CONTROL
WIRING THROUGH
GROMMET AND
SECURE WITH
CABLE TIE
GROMMET AND
CABLE TIE
USE WATERTIGHT
CONDUIT FOR HIGH
VOLTAGE
CONNECT CONDUIT
TO CUTOUT AND
ROUTE HIGH
VOLTAGE WIRING
Figure 8.
Route Control Wires
Wire Run Length
AWG#
Insulation Type
Less than 100’ (30m)
18
Temperature Rating
35°C Minimum
More than 100’ (30m)
16
Table 7. Conventional 24VAC Non-Communicating
Thermostat Wiring
Route High Voltage and Ground Wires
Any excess high voltage field wiring should be trimmed
and secured away from any low voltage field wiring. To
facilitate a conduit, a cutout is located on the bottom of
the control box. Connect conduit to the control box using a
proper conduit fitting.
Connect the 208/230 high voltage power supply from the
disconnect to the 4HP18V contactor as shown. Connect
the ground wire from the power supply to the unit ground
lug connection.