Allied 4AC13/14 Скачать руководство пользователя страница 5

507043-01

Issue 1222

 

        Page  5  of   8

Electrical Connections

Be sure to check all local codes to determ ine that the unit

is installed in accordance with local requirem ents.  Consult
the National Electric Code for wire size requirem ents.  Use
60

/

 C  or higher copper wires only.  Always provide ground

connections to the outdoor unit.  Power supply m ust agree
with rating on unit nam eplate.

Provide line voltage power supply to unit from  a properly

sized disconnect switch.  Route power and ground wires
from  disconnect switch to unit.  Line voltage connections
are m ade at the line side of the contactor in the control box
of the outdoor unit.  Follow the  wiring diagram  attached to
inside of the access panel.

Proper circuit protection recom m endations are  indicated

on Unit Rating Plate. Tim e delay fuses are required to
prevent blowing due to starting current (the current in rush
when equipm ent starts is referred to as the Locked Rotor
Am ps or (LRA). 

Rem ove access panel to gain access to unit wiring.

Extend wires from  disconnect through power wiring hole
provided and into unit control box.  Flexible conduit is
required for the swing out control box feature.

Connect ground wire to ground connection in control box

for safety.  Connect power wiring to contactor.

High voltage power connections to 3-phase m odels is

m ade to "Pig Tail" leads with field supplied splice
connectors.

Control W iring

The control voltage is 24 Vac. NEC Class I insulated 18

AW G is required for control wiring.  For lengths longer than
150 feet, contact your local distributor for technical service.

Ensure the room  therm ostat is properly installed per

instructions shipped with room  therm ostat.  Generally the

therm ostat should not be exposed to sunlight, drafts or
vibration and should not be m ounted on exterior walls.

Low voltage connections should be in accordance to the

wiring diagram .

Typical Low  Voltage Connection

Start-Up Procedure

1.

Close electrical disconnects to energize system .

2.

Set room  therm ostat at desired tem perature.  Be
sure set point is below indoor am bient tem perature.

3.

Set the system  switch of the therm ostat on COOL
and fan switch for continuous operation (ON) or
AUTO, as desired.

4.

Adjust refrigerant charge per "Adjusting Charge"
section.

Adjusting Charge

Factory charge is shown on the rating label located on

the access panel.

All units are  factory charged for 15 feet of

connecting line set. 

  Charge should be adjusted for line

set lengths other than 15 feet.  For line sets shorter than 15
feet in length, rem ove charge.  For line sets longer than 15
feet, add charge.  Oil charge is sufficient for all line lengths.

Before final adjustm ent is m ade to the refrigerant charge,

check for proper indoor airflow.  Recom m ended airflow is

350-450 CFM  per ton

 (12,000 Btuh) through a 

w et coil

.

Refer to indoor unit instructions for m ethods of determ ining
air flow and blower perform ance.

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power before connecting unit,
perform ing any m aintenance or rem oving panels or
doors.  More than one disconnect m ay be required to
turn off all power.

FAILURE TO DO SO CO ULD RESULT IN BODILY
INJURY OR DEATH.

. . . .

T he unit cabinet m ust have an uninterrupted or
unbroken ground.  The ground m ust be installed in
accordance with all electrical codes.  Failure to follow
this warning can result in an injury, fire, or death.

Refrigeration Charge Adjustm ent

Liquid Line Diam eter

Oz. Per Linear Foot 

3/8"

.6

Low voltage wiring m ust be separated from  high
voltage wiring.

Содержание 4AC13/14

Страница 1: ...onal state or local codes in any way These instructions must be left with the property owner Manufactured By Allied Air Enterprises LLC A Lennox International Company 215 Metropolitan Drive West Columbia SC 29170 P507043 01 P 507043 01 4AC13 14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residen...

Страница 2: ... approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdoor Section Zoning ...

Страница 3: ...ervice side should be 24 and 48 on top On a solid level foundation or pad To minimize refrigerant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top ...

Страница 4: ...e a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of leak check relieve all pressure from system before evacuation Evacuating And Charging Instructions These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing 1 Connect the vacuum ...

Страница 5: ...ns shipped with room thermostat Generally the thermostat should not be exposed to sunlight drafts or vibration and should not be mounted on exterior walls Low voltage connections should be in accordance to the wiring diagram Typical Low Voltage Connection Start Up Procedure 1 Close electrical disconnects to energize system 2 Set room thermostat at desired temperature Be sure set point is below ind...

Страница 6: ...low and add charge if superheat is high Units with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermist...

Страница 7: ...507043 01 Issue 1222 Page 7 of 8 A C SINGLE PHASE WIRING DIAGRAM ...

Страница 8: ...es can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surfaces For maximum protection of th...

Отзывы: