A - 

Open both manifold valves and start the vacuum pump.

B - 

Evacuate the line set and indoor unit to an 

absolute pressure

 of 23,000 microns (29.01 inches of mercury).

NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure

indicates a relatively large leak. If this occurs, 

repeat the leak testing procedure.

NOTE - The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute

pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C - 

When the  absolute  pressure  reaches  23,000  microns  (29.01  inches  of

mercury), perform the following:

Close manifold gauge valves.
Close valve on vacuum pump.
Turn off vacuum pump.
Disconnect manifold gauge center port hose from vacuum pump.
Attach  manifold  center  port  hose  to  a  nitrogen  cylinder  with  pressure

regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor

unit.
Close manifold gauge valves.

D - 

Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the

nitrogen from the line set and indoor unit.

E - 

Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the

absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump

and closing the manifold gauge valves.

F - 

When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a

cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the

line set and indoor unit.

G - 

Perform the following:

Close manifold gauge valves.
Shut off HFC-410A cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core

tool while maintaining a positive system pressure.
Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6) of a turn as illustrated.

OUTDOOR

UNIT

TO VAPOR

SERVICE VALVE

TO LIQUID LINE

SERVICE VALVE

MICRON

GAUGE

VACUUM PUMP

1/4 SAE TEE WITH SWIVEL

COUPLER

500

MANIFOLD

GAUGE SET

HFC-410A

RECOMMEND

MINIMUM 3/8” HOSE

A - 

Connect low side of manifold gauge set with

1/4 SAE in-line tee to 

vapor 

line service valve

B - 

Connect high side of manifold gauge set to

liquid 

line service valve

C - 

Connect available micron gauge connector

on the 1/4 SAE in-line tee.

D - 

Connect the  vacuum pump (with vacuum

gauge)  to  the  center  port  of  the  manifold

gauge set. The center port line will be used

later for both the HFC-410A and nitrogen

containers.

HIGH

LOW

1

2

3

4

5

6

7

8

9

10

11 12

1/6 TURN

NITROGEN

3

CONNECT GAUGE SET

A

B

C

D

4

EVACUATE THE SYSTEM

NOTE - Remove cores from service valves (if not already done).

Possible equipment damage.
Avoid deep vacuum operation. Do not use

compressors  to  evacuate  a  system.

Extremely low vacuum can cause internal

arcing  and  compressor  failure.  Damage

caused  by  deep  vacuum  operation  will

void warranty.

WARNING !

NOTE -

ister  to  deliver  liquid

refrigerant.

EVACUATION

FIGURE 9 

Содержание 18H86A

Страница 1: ... SPLIT SYSTEM HEAT PUMP R410A REFRIGERANT IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant CFCs HCFCs and HFCs as of July 1 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may be levied for noncompliance CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Tak...

Страница 2: ...ider any weather conditions especially wind that may cause panels to be blown around and damaged IMPORTANT Exhaust vents from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit This will diminish ...

Страница 3: ...eld Fabricated NOTE Some applications may require a field provided 7 8 to 1 1 8 adapter NOTE When installing refrigerant lines longer than 50 feet refer to the Refrigerant Piping Design and Fabrica tion Guidelines manual WARNING When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system use a regulator that can control the pressure down to 1 or 2 psig ...

Страница 4: ...d line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A HCFC 22 cylinder with clean refrigeran...

Страница 5: ... ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVICE PORT CAP CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION 3 VAPOR LINE SERVICE VALV...

Страница 6: ... cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 ...

Страница 7: ... bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 4 Attach t...

Страница 8: ... 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauges from service ports After the line set has been connected to the indoor and ...

Страница 9: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Rein...

Страница 10: ...ay result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic d...

Страница 11: ...SPECIFIC THERMOSTAT AND INDOOR UNIT REVERSING VALVE POWER COMMON 1ST STAGE AUX HEAT INDOOR BLOWER COMPRESSOR POWER COMMON EMERGENCY HEAT Low Voltage Wiring with Auxiliary Heat HIGH VOLTAGE FIELD WIRING LOW VOLTAGE FIELD WIRING FACTORY WIRING FIGURE 11 STEP 5 UNIT START UP IMPORTANT If unit is equipped with a crankcase heater it should be energized 24 hours before unit start up to prevent compresso...

Страница 12: ...TEM SHOWN CLOSED INSERT HEX WRENCH HERE SERVICE PORT CORE SERVICE PORT CAP ANGLE TYPE SERVICE VALVE FRONT SEATED CLOSED STEM CAP VALVE STEM SHOWN OPEN INSERT HEX WRENCH HERE ANGLE TYPE SERVICE VALVE BACK SEATED OPENED 1 Remove stem cap with an appropriately sized wrench 2 Use a service wrench with a hex head extension 3 16 for liquid line valve sizes and 5 16 for vapor line valve sizes to back the...

Страница 13: ...ds going in and out of the defrost mode when the compressor delay jumper is installed Factory default is jumper installed NOTE The 30 second compressor feature is ignored when jumpering the TEST pins Time Delay The timed off delay is five minutes long The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is by...

Страница 14: ...ingle thermostat demand To reset a 5 strike pressure switch lockout cycle 24V control power to the defrost control or place the defrost control in the TEST mode by shorting the TEST pins for 2 seconds Homeowners Information CAUTION Beforeattemptingtoperformanyserviceormaintenance turn the electrical power to unit OFF at disconnect switch In order to ensure peak performance your system must be prop...

Страница 15: ...pump In EMERGENCY HEAT mode all heating demand is sat isfied by auxiliary heat heat pump operation is locked out After a six hour compressor crankcase warm up period the thermostat can be switched to the HEAT setting and normal heat pump operation may resume Professional Maintenance NOTICE Failure to follow instructions will cause damage to the unit This unit is equipped with an aluminum coil Alum...

Страница 16: ... will turn on the air conditioner to check operating functions such as the startup and shutoff operation He will also check for unusual noises or odors and measure indoor outdoor temperatures and system pressures as needed He will check the refrigerant charge per the charging sticker information on the outdoor unit 2 Verify that system total static pressure and airflow settings are within specific...

Отзывы: