Allied 18H86A Скачать руководство пользователя страница 4

Page 4

STEP 2 – REFRIGERANT PIPING – (Continued) 

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

 A -

On fully cased coils, remove the coil access and plumbing panels.

 B -

sembly.

 C -

Using two wrenches, disconnect liquid line from liquid line 

ing. T

cess.

 D -

Remove and discard fixed orifice, valve stem assembly (if present)

and Teflon

®

 washer as illustrated above.

 E -

Use a field-provided fitting to temporarily reconnect the liquid line to the

indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE 

(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL

PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER

LINE

CHECK

EXPANSION

VALVE

TEFLON®

RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

 A -

On fully cased coils, remove the coil access and plumbing panels.

 B -

Remove any shipping clamps from the liquid line and distributor

assembly.

 C -

Disconnect the  equalizer  line  from  the  check  expansion  valve

equalizer line fitting on the vapor line.

 D -

Remove the vapor line sensing bulb.

 E -

Disconnect the liquid line from the check expansion valve at the

liquid line assembly.

 F -

Disconnect the check expansion valve from the liquid line orifice

housing. Take care not to twist or damage distributor tubes during

this process.

 G -

Remove and discard check expansion valve and the two Teflon

®

rings.

 H -

Use a field-provided fitting to temporarily reconnect the liquid line to

the indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING

CLEAN HCFC-22 TO BE

USED FOR FLUSHING

(Positioned to deliver liquid

refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK

RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

VAPO
R

LIQUID

1

 A -

HCFC-22 cylinder with clean refrigerant (positioned to deliver liquid

refrigerant) to the vapor service valve.

 B -

HCFC-22 gauge set (low side) to the liquid line valve.

 C -

HCFC-22 gauge set center port to inlet on the recovery machine with an

empty recovery tank connected to the gauge set.

 D -

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

 A -

Set the recovery machine for liquid recovery and start the recovery

machine.  Open  the  gauge  set  valves  to  allow  the  recovery

machine to pull a vacuum on the existing system line set and indoor

unit coil.

 B -

Position  the  cylinder  of  clean  HCFC-22  for  delivery  of  liquid

refrigerant and open its valve to allow liquid refrigerant to flow into

the system through the vapor line valve. Allow the refrigerant to

pass from the cylinder and through the line set and the indoor unit

coil before it enters the recovery machine.

 C -

After all of the liquid refrigerant has been recovered, switch the

recovery machine to vapor recovery so that all of the HCFC-22

vapor is recovered. Allow the recovery machine to pull the system

down to 0.

 D -

Close the valve on the inverted HCFC-22 drum and the gauge set

valves.  Pump  the  remaining  refrigerant  out  of  the  recovery

machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the same

amount of clean refrigerant that previously charged the system. Check

the charge in the flushing cylinder before proceeding.

1A

2

3

1B

FIGURE 4 

Содержание 18H86A

Страница 1: ... SPLIT SYSTEM HEAT PUMP R410A REFRIGERANT IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant CFCs HCFCs and HFCs as of July 1 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may be levied for noncompliance CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Tak...

Страница 2: ...ider any weather conditions especially wind that may cause panels to be blown around and damaged IMPORTANT Exhaust vents from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit This will diminish ...

Страница 3: ...eld Fabricated NOTE Some applications may require a field provided 7 8 to 1 1 8 adapter NOTE When installing refrigerant lines longer than 50 feet refer to the Refrigerant Piping Design and Fabrica tion Guidelines manual WARNING When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system use a regulator that can control the pressure down to 1 or 2 psig ...

Страница 4: ...d line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A HCFC 22 cylinder with clean refrigeran...

Страница 5: ... ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVICE PORT CAP CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION 3 VAPOR LINE SERVICE VALV...

Страница 6: ... cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 ...

Страница 7: ... bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 4 Attach t...

Страница 8: ... 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauges from service ports After the line set has been connected to the indoor and ...

Страница 9: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Rein...

Страница 10: ...ay result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic d...

Страница 11: ...SPECIFIC THERMOSTAT AND INDOOR UNIT REVERSING VALVE POWER COMMON 1ST STAGE AUX HEAT INDOOR BLOWER COMPRESSOR POWER COMMON EMERGENCY HEAT Low Voltage Wiring with Auxiliary Heat HIGH VOLTAGE FIELD WIRING LOW VOLTAGE FIELD WIRING FACTORY WIRING FIGURE 11 STEP 5 UNIT START UP IMPORTANT If unit is equipped with a crankcase heater it should be energized 24 hours before unit start up to prevent compresso...

Страница 12: ...TEM SHOWN CLOSED INSERT HEX WRENCH HERE SERVICE PORT CORE SERVICE PORT CAP ANGLE TYPE SERVICE VALVE FRONT SEATED CLOSED STEM CAP VALVE STEM SHOWN OPEN INSERT HEX WRENCH HERE ANGLE TYPE SERVICE VALVE BACK SEATED OPENED 1 Remove stem cap with an appropriately sized wrench 2 Use a service wrench with a hex head extension 3 16 for liquid line valve sizes and 5 16 for vapor line valve sizes to back the...

Страница 13: ...ds going in and out of the defrost mode when the compressor delay jumper is installed Factory default is jumper installed NOTE The 30 second compressor feature is ignored when jumpering the TEST pins Time Delay The timed off delay is five minutes long The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is by...

Страница 14: ...ingle thermostat demand To reset a 5 strike pressure switch lockout cycle 24V control power to the defrost control or place the defrost control in the TEST mode by shorting the TEST pins for 2 seconds Homeowners Information CAUTION Beforeattemptingtoperformanyserviceormaintenance turn the electrical power to unit OFF at disconnect switch In order to ensure peak performance your system must be prop...

Страница 15: ...pump In EMERGENCY HEAT mode all heating demand is sat isfied by auxiliary heat heat pump operation is locked out After a six hour compressor crankcase warm up period the thermostat can be switched to the HEAT setting and normal heat pump operation may resume Professional Maintenance NOTICE Failure to follow instructions will cause damage to the unit This unit is equipped with an aluminum coil Alum...

Страница 16: ... will turn on the air conditioner to check operating functions such as the startup and shutoff operation He will also check for unusual noises or odors and measure indoor outdoor temperatures and system pressures as needed He will check the refrigerant charge per the charging sticker information on the outdoor unit 2 Verify that system total static pressure and airflow settings are within specific...

Отзывы: