507582-04
Page 48 of 54
Issue 2220
Model
Gas
Manifold Pressure in w.g.
Supply Line
Pressure in
w.g.
0 - 10000 ft.
0 - 4500 ft.
4501 - 5500 ft.
5501 - 6500ft.
6501 - 7500ft.
7501-10000ft.
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Min.
Max.
All Models
Natural
1.7
3.5
1.6
3.3
1.5
3.2
1.5
3.1
1.7
3.5
4.5
13.0
Lp/
Propane
4.5
10.0
4.2
9.4
4.0
9.1
3.9
8.9
4.5
10.0
11.0
13.0
Table 18.
Manifold and Supply Line Pressure 0 - 10,000 ft.
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in Table
16. If manifold pressure matches Table 18 and rate is
incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
NOTE:
To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
A pressure post on the inlet side of the gas valve provides
access to the supply pressure. Back out the 3/32 Hex screw
one turn, connect a piece of 5/16” tubing and connect a
manometer to measure supply pressure.
NOTE:
Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to re-
tighten the 3/32 Hex screw.
Manifold Pressure Measurement
1. A manifold post located on the gas valve provides
access to the manifold pressure. See Figure 60. Back
out the 3/32 Hex screw one turn, connect a piece of
5/16” tubing and connect to a manometer to measure
manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
3. While waiting for the unit to stabilize, observe the
flame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
NOTE:
Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to re-
tighten the 3/32 Hex screw.
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue
outlet and compare to the table below. The maximum
carbon monoxide reading should not exceed 100 ppm.
Model
CO
2
% For Nat
CO
2
% For LP
Low Fire
High Fire
Low Fire
High Fire
045
5.6 - 6.6
7.8 - 8.8
6.6 - 7.6
9.1 - 10.1
070
5.6 - 6.5
7.3 - 8.3
6.5 - 7.5
8.6 - 9.6
090
5.9 - 6.9
7.8 - 8.8
6.9 - 7.9
9.1 - 10.1
110
6.63 - 7.3
8.2 - 9.2
7.3 - 8.3
9.5 - 10.5
The maximum carbon monoxide reading should not exceed
100 ppm.
Table 17.
High Altitude Information
NOTE:
In Canada, certification for installations at
elevations over 4500 feet (1371 m) is the jurisdiction of
local authorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level without manifold adjustment. Units installed
at altitude of 4501 - 10,000 feet (1371 to 3048 m) may
require a pressure switch change which can be ordered
separately. Table 19 lists conversion kit and pressure
switch requirements at varying altitudes.
The combustion air pressure switch is factory-set and
requires no adjustment.
NOTE:
A natural to LP/propane gas changeover kit is
necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
Содержание 045-12
Страница 3: ...507582 04 Page 3 of 54 Issue 2220 Figure 1 Parts Arrangement ...
Страница 42: ...507582 04 Page 42 of 54 Issue 2220 Table 15A Field Wiring Applications with Conventional Thermostat ...
Страница 43: ...507582 04 Page 43 of 54 Issue 2220 Table 15B Field Wiring Applications with Conventional Thermostat Continued ...