Page 11

Issue 1008

x

 3600 x

= Cubic Feet Per Revolution

BTU/HR
 INPUT

 # Seconds Per Revolution

Heating

Value

For Natural Gas: 

 Check the gas input rate by observing

the gas meter, when available, making sure all other gas
appliances are turned off.  The test hand on the meter should
be timed for at least one revolution.  Note the number of
seconds for one revolution.

Cooling System

The cooling system is a complete factory package
utilizing an air-cooled condenser.  The compressor is
hermetically sealed and base mounted with rubber-
insulated hold-down bolts.

Unit compressors have internal protection.  In the
event there is an abnormal rise in the temperature of
the compressor, the protector will open and cause the
compressor to stop.

Cooling Sequence of Operation

When the thermostat calls for cooling, R is closed to G
and Y (see the wiring diagrams beginning on page 15).
This action completes the low voltage control circuit,
energizing the compressor, condenser fan motor, and
blower motor.

Blower Delay – Cooling

The circulating air blower is controlled by a timing
circuit in the integrated blower/ignition control.
Timings are not adjustable.  Blower “on” delay is 5
seconds after the compressor starts and blower “off”
timing is 90 seconds after the cooling system shuts
d o w n .

System Performance

This equipment is a self contained, factory optimized
refrigerant system, and should require no
adjustments when properly installed.  If however unit
performance is questioned, perform the following
checks.

OPERATION

The heating value of the gas can be obtained from the local
utility company.

For Propane Gas: 

 The only check for the gas input rate is to

properly adjust the manifold pressure using a manometer.
Typical manifold set point for installations at altitudes from 0 to
4500 feet above sea level is 10.0" W.C.

Temperature Rise

Check the temperature rise and, if necessary, adjust blower
speed to maintain temperature rise within the range shown
on the unit rating plate.

High Altitude

Ratings are shown on the rating plate for elevations up to
4500 feet.  For elevations above 4500 feet, ratings should
be reduced at a rate of 4% for each 1000 feet above sea
level.  See the National Fuel Gas Code Z223.1 (latest edition)
or the Canadian Installation Codes CAN/CGA-B149.1 &
B149.2 for further details.

Secure Owner’s Approval

When the system is functioning properly, secure the owner’s
approval.  Show the owner the location of all disconnect
switches and the thermostat. Instruct the owner on how to
start and stop the unit and how to adjust temperature settings
within the limitations of the system.

Suction Superheat

Table 3

Series

Suction Superheat
 +/-3 Deg°F @ ARI
 Conditions 82° OD,
80° IDDB/67° IDWB

4PGE13

Size

24

17

Liquid Line Subcooling
     +/-2 Deg°F @ ARI
    Conditions 82° OD,
    80° IDDB/67° IDWB

-

30

36
42

48
60

24,30

36

42
48
60

4PGE15

15
19
13

18

15

-

-
-

-

-

12
15

10

7

8

-
-
-
-

-

Содержание 4PGE

Страница 1: ...it WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4PGE SG 13 15 Series Gas Heating Electric Cooling Package Unit Save these instructions for future reference The installation of the furnace wiring...

Страница 2: ...er charge and airflow may reduce energy efficiency and shorten equipment life Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident...

Страница 3: ...pers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the unit Return air temperature must be maintained between 60 F 16 C and 80 F 27 C Air filte...

Страница 4: ...above any door window or gravity air inlet into the building The vent system shall terminate at least 3 above any forced air inlet located within 10 The unit shall be installed in a manner such that s...

Страница 5: ...nnected to the venting system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system...

Страница 6: ...pening Filters Air filters are to be used with this heating cooling unit Filters are not factory supplied in the unit However a filter frame accessory is available from the manufacturer that allows fi...

Страница 7: ...trap drip leg shall be installed as close as practical to the gas supply inlet of the unit LPG Propane Units Tanks and Piping Units are shipped equipped for natural gas but can be converted to LPG pro...

Страница 8: ...wiring must be sized to carry minimum circuit ampacity marked on the unit Use copper conductors only Each unit must be wired with a separate branch circuit and be properly fused Thermostat The room t...

Страница 9: ...Used WITHOUT ECONOMIZER L2 L1 POWER WIRING 208 230 1 60 75 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 GROUND SCREW SINGLE PHASE L1 L2 L3 GROUND SCREW POWER WIRING 200 230 3 60 460 575 3 6...

Страница 10: ...hould the supply pressure during standby exceed 13 w c nor should it be less than 5 w c for For Your Safety Read Before Lighting natural gas or 11 W C for propane gas with the burners in operation If...

Страница 11: ...contained factory optimized refrigerant system and should require no adjustments when properly installed If however unit performance is questioned perform the following checks OPERATION The heating v...

Страница 12: ...t work for air leaks as well as restrictions and blower speed settings If unit performance remains questionable remove charge evacuate to 500 Microns and weigh in refrigerant to name plate charge It i...

Страница 13: ...loperateswhenahightemperature condition caused by inadequate airflow occurs This causes the ignition control to close the gas valve The circulation air blower continues to operate in this situation Pr...

Страница 14: ...low tipping of the natural gas burner flame or long yellow tips on propane may be caused by lint accumulation or dirt inside the burner or burner ports at the air inlet between the burner and manifold...

Страница 15: ...506488 01 Page 15 Issue 1008 Figure 11 Connection Diagram Single Phase PSC Motor...

Страница 16: ...N 75 C WIRE WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES HEAT ANTICIPATION SETTING 0 70 AMP LINE VOLTAGE FIELD INSTALLED SEE BLOWER SPEED CHART BLK S...

Отзывы: