Electrical Specifications
Voltage Designation
Standard
Code
Voltage
Cycle
Phase
Wire
Full
Load
Amps
Breaker
AWG
mm2
D
220-240
50
3
3
7
15
14
2.5
O
208-240
60
3
3
7
15
14
2.5
NOTE: Wire sizes shown are for copper, THHN, 90° conductor per National Electric Code, article 310.
Table 8
WARNING
Ensure that a ground wire from a proven earth
ground is connected to the ground lug near the input
power block on this machine. Without proper
grounding, personal injury from electric shock could
occur and machine malfunctions may be evident.
SW008
IMPORTANT: Installation shall conform with local co-
des or, in absence of local codes, with the National
Electric Code ANSI/NFPA No. 70. Overloaded or under-
sized lines, or any low voltage condition will burn out
motors and solenoid windings.
Drain Connection
A flexible connection must be made to a vented drain system to
prevent damage to rigid drain pipes. Drain should be vented to
ensure proper flow and prevent siphoning. If proper drain size is
not available or practical, a surge tank is required. A surge tank
along with a sump pump should be used when gravity drainage is
not possible.