![ALLIANCE POM100 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/alliance/pom100/pom100_user-manual_2901153046.webp)
Power Meter
–
POM100
User Manual v1
www.compressedairalliance.com
46
Register Alias Register
Address
Action
R/WC
Size
Type
Units
Description
S3
2175
R
2
Float32
kVA
Apparent Power
Phase 3
STotal
2177
R
2
Float32
kVA
Total Apparent
Power
Energy
The energy values automatically reset to 0 when total energy reaches the limit of 1.0
x 10
9
kWh, 1.0 x 10
9
kVarh, or 1.0 x 10
9
kVah
Register Alias
Register
Address
Action
R/WC
Size
Type Units
Description
Active Energy
EP1Imp
4000
R
2
UInt32 kWh Active Energy Import
Phase 1
EP2Imp
4002
R
2
UInt32 kWh Active Energy Import
Phase 2
EP3Imp
4004
R
2
UInt32 kWh Active Energy Import
Phase 3
EPsumImp
4006
R
2
UInt32 kWh Total Active Energy
Import Phase All
EP1Exp
4008
R
2
UInt32 kWh Active Energy Export
Phase 1
EP2Exp
4010
R
2
UInt32 kWh Active Energy Export
Phase 2
EP3Exp
4012
R
2
UInt32 kWh Active Energy Export
Phase 3
EPsumExp
4014
R
2
UInt32 kWh Total Active Energy
Export Phase All
Содержание POM100
Страница 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail No Display Model POM100 ...
Страница 18: ...Power Meter POM100 User Manual v1 www compressedairalliance com 18 3PH4W no VT 3PH3W no VT A B C B C N A ...
Страница 19: ...Power Meter POM100 User Manual v1 www compressedairalliance com 19 3PH3W with VT A C B ...
Страница 20: ...Power Meter POM100 User Manual v1 www compressedairalliance com 20 1PH3W LL N 1PH2W L N L L N L N ...
Страница 21: ...Power Meter POM100 User Manual v1 www compressedairalliance com 21 1PH2W L L L N ...