Update Rate
Data acquisition rate
400ms
Calibration
Current
Per phase, all
Voltage
Per phase, all
Power factor
Per phase, all
Energy
Reset to “0” EP, EQ, ES all phase
EMC
Electrostatic discharge
Level IV (IEC61000-4-2)
Immunity to radiated
fields
Level III (IEC61000-4-3)
Immunity to fast
transients
Level IV (IEC61000-4-4)
Immunity to surge
Level IV (IEC61000-4-5)
Conducted immunity
Level III (IEC61000-4-6)
Immunity to power
frequency magnetic
fields
0.5mT (IEC61000-4-8)
Conducted and radiated
emissions
Class B (EN55022)
Standard compliance
EN 62052-11, EN61557-12, EN 62053-21, EN 62053-22, EN 62053-23, EN 50470-1,
EN 50470-3, EN 61010-1, EN 61010-2, EN 61010-031
Modbus RS485
Communication
Transmission mode
RS485 port, Half duplex