![ALLIANCE POM100 Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/alliance/pom100/pom100_user-manual_2901153028.webp)
Power Meter
–
POM100
User Manual v1
www.compressedairalliance.com
28
No.
Alias
Type
Range (decimal)
Description
9
CRC-16 Check
UInt16
-
Little-Endian
(Sending order)
Response data format:
No.
Alias
Type
Range
(decimal)
Description
1
Salve ID
UInt8
1-247
2
Function code
UInt8
16
3
Registers Start address
UInt16
300
Big-Endian
4
Registers Numbers
UInt16
1-123
Big-Endian
5
CRC-16 Check
UInt16
-
Little-Endian
Attention:
Function code (0x10=16) can only write data to “Command
Register
,
That is, only registers starting from 300 can be written data.
For example: Configure “Digital Outputs” (command=1005)
No.
Alias
Type
Range
(decimal)
Range
(hexadecimal)
Description
1
Salve ID
UInt8
1
01
2
Function code
UInt8
16
10
3
Registers Start
address
UInt16
300
012C
Big-Endian
(Sending order)
4
Registers Numbers
UInt16
2
0002
Big-Endian
(Sending order)
5
Bytes of Registers
Values
UInt8
4
04
Содержание POM100
Страница 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail No Display Model POM100 ...
Страница 18: ...Power Meter POM100 User Manual v1 www compressedairalliance com 18 3PH4W no VT 3PH3W no VT A B C B C N A ...
Страница 19: ...Power Meter POM100 User Manual v1 www compressedairalliance com 19 3PH3W with VT A C B ...
Страница 20: ...Power Meter POM100 User Manual v1 www compressedairalliance com 20 1PH3W LL N 1PH2W L N L L N L N ...
Страница 21: ...Power Meter POM100 User Manual v1 www compressedairalliance com 21 1PH2W L L L N ...