background image

1.   Make certain your dryer is equipped for use with the type of

gas in your laundry room. Dryer is equipped at the factory for
Natural Gas with a 3/8 inch NPT gas connection.

NOTE: The gas service to a gas dryer must conform
with the local codes and ordinances, or in the ab-
sence of local codes and ordinances, with the latest
edition of the National Fuel Gas Code ANSI Z223.1/
NFPA 54 or the CAN/CSA-B149.1 Natural Gas and
Propane Installation Code.

Natural Gas, 1000 Btu/ft

3

 [37.3 MJ/m

3

], service must be supplied

at minimum 5.0 inch water column pressure to maximum 10.5
inch water column pressure.

For proper operation at altitudes above 3000 feet [915 m] the nat-
ural gas valve spud orifice size must be reduced to ensure com-
plete combustion. Refer to 

Table 3 

.

Natural Gas Altitude Adjustments

Altitude

Orifice Size

Part

No.

feet [m]

No.

inches [mm]

3000 [915]

43

0.0890 [2.26]

D503778

6000 [1830]

44

0.0860 [2.18]

58719

8000 [2440]

45

0.0820 [2.08]

D503779

9000 [2740]

46

0.0810 [2.06]

D503780

10,000 [3050]

47

0.0785 [1.99]

D503781

Table 3

2.   Remove the shipping cap from the gas connection at the rear

of the dryer. Make sure you do not damage the pipe threads
when removing the cap.

NOTE: If gas supply connection is British Standard
Pipe Tapered thread (BSPT), order 44178804 brass
female NPT (FPT) to male BSPT gas pipe thread
adapter, available at extra cost.

3.   Connect to gas supply pipe using thread sealant or Teflon

tape. Torque 90 - 175 inch-pounds [10.2 - 19.7 Nm].

NOTE: The connection of gas supply to the appli-
ance shall be made with a flexible hose suitable for
the appliance category in accordance with national
installation regulations of the country of destina-
tion. If in doubt contact the dryer distributor or man-
ufacturer.

NOTE: When connecting to a gas line, an equipment
shut-off valve in accordance with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and the Natural
Gas and Propane Installation Code, CSA B149.1
must be installed within 6 feet [1.8 m] of the dryer.
An 1/8 in. NPT pipe plug must be installed as shown
for checking inlet pressure. Refer to 

Figure 5 

.

Starting Serial No. 1908000001, the following must be furnished
and installed by the customer for the gas service line to dryer:
Union at gas supply connection (listed to ANSI Z21.24 and CSA
6.10).

D233I_SVG

2

3

4

1

5

1.  

New Stainless Steel Flexible Connector – (Use design
CSA certified connector) Use only if allowed by local co-
des

2.  

1/8 in. NPT Pipe Plug

3.  

Equipment Shut-Off Valve

4.  

Black Iron Pipe:

Shorter than 20 ft. [6.1 m] – Use 3/8 in. [9.5 mm] pipe.

Longer than 20 ft. [6.1 m] – Use 1/2 in. [12.7 mm] pipe.

5.  

3/8 in. NPT Gas Connection

Figure 5

4.   Tighten all connections securely but don't overtighten to avoid

breaking or bending the gas valve bracket. Turn on gas and
check all pipe connections (internal & external) for gas leaks
with a non-corrosive leak detection fluid.

NOTE: The dryer and its appliance main gas valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test pres-
sures in excess of 1/2 psi [3.45 kPa]. Refer to 

Check

Heat Source

.

NOTE: DO NOT connect the dryer to L.P. Gas Service
without converting the gas valve. Install L.P. Gas Con-
version Kit 649P3, available at extra cost.

Installation

©

 Copyright, Alliance Laundry Systems LLC -

 DO NOT COPY or TRANSMIT

  14

  Part No. D514320ENR5

Содержание Speed Queen DF7000SE

Страница 1: ...ginal Instructions Keep These Instructions for Future Reference CAUTION Read the instructions before using the machine If this machine changes ownership this manual must accompany machine www speedque...

Страница 2: ......

Страница 3: ...user smells gas The gas utility instructions plus the SAFETY and WARNING note directly above must be posted in a prominent location near the dryer for customer use WARNING Installation of unit must b...

Страница 4: ...r or gas fitter This appliance must be installed with a 36 inch 910 mm long flexible gas connector A T Handle type gas shut off valve must be installed in the gas supply line to this appliance This ap...

Страница 5: ...hree Wire Plug 15 Connecting Power Cord with Four Wire Plug 17 Reverse Door if Desired 18 Wipe Out Inside of Dryer 20 Plug In the Dryer 20 Electric Dryer 20 Gas Dryer 20 Recheck Steps 21 Check Heat So...

Страница 6: ...mm D 4 in 102 mm E 15 4 in 391 mm F 26 875 in 683 mm G 4 5 in 114 mm H 0 4 in 10 mm I 8 in 203 mm J 28 in 711 mm K 23 5 in 597 mm NOTE Exhaust openings are 4 inch 102 mm metal ducting With leveling le...

Страница 7: ...102 mm metal ducting With leveling legs turned into base NOTE Gas models cannot be vented out left side of cabinet because of burner housing IMPORTANT The dryer should have sufficient clear ance arou...

Страница 8: ...e of the dryer 7 Plug in the dryer 8 Recheck steps 9 Start and run the dryer in a heat setting to verify dryer is heat ing Position and Level the Dryer 1 Install dryer before washer This allows room f...

Страница 9: ...DRY2500N_SVG 3 2 1 1 Dryer Base 2 Level 3 Leveling Leg Figure 2 Installation Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 9 Part No D514320ENR5...

Страница 10: ...oor DRY2641N_SVG H E D C A 3 1 Front View Closet Door DRY2637N_SVG F F 2 G 1 Closet Door 2 Centered Air Openings G 2 Openings minimum 3 Outer Wall of Enclosure Figure 3 Installation Copyright Alliance...

Страница 11: ...e time of installation Order No 526P3 Hold Down Kit availa ble at extra cost for a manufactured mobile home in stallation Follow the instructions supplied with the kit Installation of unit must confor...

Страница 12: ...exhaust duct 2 feet 610 mm from dry er check with dryer running and no load Exhausting dryer in hard to reach locations can be done by installing 521P3 Flexible Metal Vent Kit available as option al...

Страница 13: ...risk of gas leaks fire or explosion The dryer must be connected to the type of gas as shown on nameplate located in the door re cess Use a new flexible stainless steel connector Use pipe joint compoun...

Страница 14: ...or the appliance category in accordance with national installation regulations of the country of destina tion If in doubt contact the dryer distributor or man ufacturer NOTE When connecting to a gas l...

Страница 15: ...es and ordinances WARNING Improper connection of the equipment earth ground conductor can result in a risk of electric shock Check with a qualified electrician or service person if you are in doubt as...

Страница 16: ...rth Ground Neutral 120 240 Volt 60 Hertz AC 1 Phase Service Entrance Switch Box Refer to NOTE above 8 30 Ampere Fuses or Circuit Breaker 9 Neutral Wire 10 Metallic or Non Metallic Sheathed Cable Coppe...

Страница 17: ...inuity of the earth ground connection before plugging the cord into an outlet Use an acceptable indicating device connected to the center earth ground pin of the plug and the green screw on the back o...

Страница 18: ...1 terminal b Black wire to L2 terminal c White wire to Neutral terminal NOTE When installing the white wire loop the free eyelet end of the earth ground to neutral wire re moved in Step 3 and attach a...

Страница 19: ...r panel DRY1916N_SVG B A Figure 17 4 Rotate door panel 180 degrees as shown D273P_SVG Figure 18 5 Remove door strike from door liner and reinstall on opposite side DRY1917N_SVG Figure 19 6 Insert line...

Страница 20: ...ion on connecting power cord Connect to 30 Amp Circuit D275I_SVG2 Figure 25 Gas Dryer Dryer requires 120 Volt 60 Hertz electrical supply and comes equipped with a 3 prong earth ground plug Refer to se...

Страница 21: ...hree prong earth ground plug for your protection against shock haz ard and should be plugged directly into a protective earth ground three prong receptacle Do not cut or remove the earth ground prong...

Страница 22: ...arsh roar ing very blue flame indicates too much air Adjust the air shutter as follows a Loosen the air shutter lockscrew b Turn the air shutter to the left to get a luminous yellow tipped flame then...

Страница 23: ...CHECK 3 GAS ONLY Connect Gas Sup ply Pipe Check for Gas Leaks D233I_SVG1 7 Plug In the Dryer Electric D275I_SVG1 Gas D254I_SVG CHECK CHECK 4 ELECTRIC ONLY Connect Electrical Cord D679I_SVG1 8 Recheck...

Отзывы: