Ignition Control Operation

Power Up

After 24 VAC is applied to the ignition control pins 
24V and GND, the Diagnostic LED on the ignition 
control will turn orange/yellow. If a fault is detected 
the ignition control will enter Lockout Mode. If no 
faults are detected, the Diagnostic LED will turn 
Green and the ignition control will enter Standby 
Mode.

Standby Mode

While in Standby Mode, the ignition control will 
continually monitor the system for faults. Once 
24VAC

 

is applied to terminals TH and GND on the 

control, the ignition control will enter Start Up Mode.

Start Up Mode

During Start Up Mode, the ignition control will 
monitor the system for faults and begin the ignition 
sequence. If no faults are present, the ignition control 
will begin the ignition sequence by entering an 18 
second waiting period. During this time the Green 
LED on the ignition control will switch between Red 
and Green, before maintaining a Green color.

After the waiting period, the ignition control will turn 
on the igniter and gas valve. The igniter will remain on 
until a flame is sensed, or up to 10 seconds.  

Once a flame has been sensed the ignition control will 
stop sparking, the gas valve will remain on and 
ignition control will enter Run Mode.

If a flame is not sensed, the ignition control will then 
begin two additional retrials for ignition. The ignition 
control will re-enter the 18 seconds waiting period 
before the ignition control makes another attempt at 
ignition. If the three attempts at ignition fail, the 
ignition control will enter Lockout Mode.

Run Mode

While in Run Mode the ignition control leaves the gas 
valve on, monitors the flame signal, and leaves the 
igniter off.  

If a flame signal is lost during Run Mode, one 
additional retrial for ignition will take place within one 
second. The ignition control will restore the spark for 
approximately 10 seconds. If the ignition re-attempt 
fails, the ignition control will enter Lockout Mode.

The ignition control will remain in Run Mode until 
24VAC is removed from terminals TH and GND on 
the control. 

Termination of Flame

The flame will go out when power is removed from 
ignition control. The ignition control will turn off the 
gas valve and enter Standby Mode.

Lockout Mode

When Lockout Mode is entered, the ignition control 
will remove power to the gas valve, the igniter will 
turn off, the Lockout/Reset Light will turn on, and the 
Diagnostic LED will display the appropriate Error 
Code.

Lockout Manual Reset

Lockout Mode is cleared by pressing an external reset 
switch for three seconds. The ignition control will 
clear all error codes and enter Standby Mode. During 
Lockout Manual Reset, the Diagnostic LED on the 
ignition control flashes red and orange, and the Reset 
Light remains on until the ignition control is reset.  
After the Reset Light turns off, stop pressing the 
switch. Holding the reset for three seconds after 
lockout has been cleared will cause a fault and result in 
entering Lockout Mode again.

Содержание 25 Pound Capacity

Страница 1: ...city 35 Pound Capacity 55 Pound Capacity Starting Serial No 0602004144 Refer to Page 3 for Model Numbers Part No 70400001R4 August 2008 Keep These Instructions for Future Reference If this machine cha...

Страница 2: ......

Страница 3: ...building Clear the room building or area of all occupants Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call t...

Страница 4: ...Service 4 Serial Plate Location 4 Wiring Diagram 4 Safety Information 5 Explanation of Safety Messages 5 Important Safety Instructions 6 Operating Instructions 8 Emergency Stop Button on CE Models 8 O...

Страница 5: ...0G2 BA030N DR30G2 BT030D DR30G2 BT030L DR30G2 BT030N DR30G2 BU030L DR30G2 BU030N IPD30G2 IT030L IPD30G2 IT030N CHD30S2 CT030S CHD30S2 CU030S DR30S2 BT030S DR30S2 BU030S IPD30S2 IT030S CHD30E2 CT030E C...

Страница 6: ...he name and address of the nearest authorized parts distributor For technical assistance call 920 748 3121 Serial Plate Location Model and serial numbers are found on serial plate on rear of machine a...

Страница 7: ...ns electrical wiring regulations and any other relevant statutory regulations Because of varied requirements applicable local codes should be thoroughly understood and all pre installation work arrang...

Страница 8: ...sonnel 15 If not installed operated and maintained in accordance with the manufacturer s instructions or if there is damage to or mishandling of this product s components use of this product could exp...

Страница 9: ...w the fabric care instructions supplied by the garment manufacturer 27 Never operate the tumbler with any guards and or panels removed 28 DO NOT operate the tumbler if it is smoking grinding has missi...

Страница 10: ...with laundry DO NOT OVERLOAD NOTE Overloading causes slow drying and wrinkling Close loading door Tumbler will not operate with the door open Step 3 Determine Control Type and Temperature Setting Ref...

Страница 11: ...future cycles IMPORTANT To stop the tumbler at any time during the cycle OPEN DOOR If the loading door or lint panel door is opened during the cycle the heating system will shut off and the motor wil...

Страница 12: ...per wiring Check control Replace if inoperative AF 1 Airflow switch closed when cycle started Check airflow switch Replace if inoperative AF 2 Airflow switch failed to close after cycle started Check...

Страница 13: ...18 hours or until door is opened Preliminary Control Information Power Up Mode When power is applied to the tumbler the control will enter Ready Mode unless a cycle was in process prior to a disruptio...

Страница 14: ...be tested When the temperature selector is changed the new setting is displayed by flashing the IN USE LED as follows High Normal 4 flashes Medium PP 3 flashes Low Delicate 2 flashes No Heat 1 flash N...

Страница 15: ...PM display when equipped with rotational sensor only Monitors the lint door switch operation Monitors the thermistor for operation The minimum drying time is 0 minutes and the minimum cooling time is...

Страница 16: ...button these buttons are used to adjust the drying time cooling time temperature clockwise time dwell time counterclockwise time and minutes per coin 4 Temperature LEDs Indicate temperature setting 5...

Страница 17: ...lows the following parameter order 1 Tumbler run time per coin DRYING COOLING time HIGH temperature setpoint MEDIUM temperature setpoint LOW temperature setpoint 2 An LED will be on to indicate which...

Страница 18: ...ing time drying temperature and diagnostic codes 5 User Program LEDs Illumination shows which user program is currently being displayed 6 Program Select This button toggles through the five user progr...

Страница 19: ...hat the buzzer will sound for 5 seconds when the drying cycle is completed ON indicates that the buzzer will sound continuously until the STOP button is pressed or the loading door is opened 7 Safety...

Страница 20: ...rogram time 11 Use the Display Select button to choose between Drying Time Cooling Time and Temperature Then use the Up Down arrows to adjust the times and temperature 12 To cancel this temporary prog...

Страница 21: ...n The ignition control will re enter the 18 seconds waiting period before the ignition control makes another attempt at ignition If the three attempts at ignition fail the ignition control will enter...

Страница 22: ...he Unexpected Presence of Flame test is performed when no flame is expected Failure of this test results in the ignition control entering Lockout Mode with the Diagnostic LED displaying Error Code 3 F...

Страница 23: ...does so Excessive gaps between the lint screen and the lint screen panel allow lint to pass into the ductwork system and may restrict airflow e Carefully wipe any accumulated lint off of the cabinet...

Страница 24: ...er before servicing Close gas shut off valve to gas tumbler before servicing Close steam valve to steam tumbler before servicing Never start the tumbler with any guards panels removed Whenever ground...

Страница 25: ...3 Check and clean steam coils if applicable 4 Check flow of combustion and ventilation air 5 Check belt tension and condition Replace worn or cracked belts Bi Annually 1 Check mounting hardware for an...

Страница 26: ...ding tumblers remove all combustible materials including lint before operating the machine Check cylinder for foreign objects to avoid damage to clothing and equipment Clean lint from lint compartment...

Страница 27: ...must be reconnected to ensure that the tumbler is properly grounded W002 WARNING Use a vacuum to clean air vents on drive motors Use a vacuum to clean lint from rear limit thermostat cover Check and...

Страница 28: ...Laundry Systems LLC DO NOT COPY or TRANSMIT Annual Maintenance Remove cylinder Use a vacuum to clean lint from area around rear seal and idler assembly Check seal idler assembly for wear Remove burne...

Страница 29: ...Won t Start Won t Heat Clothes Not Dry Possible Reason Corrective Actions Insert correct coin s or valid card if applicable Close the loading door tightly Close lint panel tightly Press the START pad...

Отзывы: