Troubleshooting
Before troubleshooting your SLC 500 system, please obtain an SLC 500 Modular Hardware
Style User Manual (1747-UM011) from one of the sources listed on page 5. Refer to the
chapter on Troubleshooting.
In addition to the SLC 500 Modular Hardware Style User Manual, the SLC 500 Instruction
Set Reference Manual (1747-RM001) may also be obtained from the sources listed on page 5.
This manual contains explanations and examples for the entire instruction set as well as for all
status words and bits. It also contains explanations for all possible fault codes found in status
word S:6.
Specifications
Operating Specifications
Specification for
1747-
SLC 5/03
SLC 5/04
SLC 5/05
L531
L532
L541
L542
L543
L551
L552
L553
Memory (words)
8K
16K
16K
32K
64K
16K
32K
64K
Maximum I/O Capacity
4096 discrete inputs / 4096 discrete outputs
Max. Local System
3 chassis / 30 slots
Programming
Instructions
99
Typical Scan Time
(1)
(1)
The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication servicing.
Actual scan times depend on your program size, instructions used, and the communication protocol.
1 ms/K
0.9 ms/K
Bit Execution (XIC)
0.44 µs
0.37 µs
Programming Software
SLC 5/03s and SLC 5/04s: RSLogix 500™, PLC-500 A.I. Series™,