10
SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
Publication 1747-IN009C-MU-P - December 2002
3.
Unplug the battery connector. Refer to the figure on page 10 for battery connector
location.
4.
Remove the battery from the retaining clips.
5.
Insert a new battery into the battery retaining clips.
6.
Plug the battery connector into the socket as shown above.
7.
Re-insert the module into the SLC 500 chassis.
8.
Restore power to the SLC 500 power supply.
9.
Close the processor door.
IMPORTANT
The SLC 5/03, 5/04, and 5/05 processors have a capacitor that
provides at least 30 minutes of battery back-up while the battery is
disconnected. Data in RAM is not lost if the battery is replaced within
30 minutes
IMPORTANT
See page 13 for information on proper battery handling, storage, and
transporting.
White
Red
Battery Connector
Left Side View
Battery