Drive Selection Considerations
Chapter
1
PowerFlex 700 Drives I/O Cassette Terminals
Table 23 - PowerFlex 700 Drives I/O Control Terminal Designations (Frames 0…6)
Terminal Name
Factory Default Description
1
Analog In 1 (–)
(1)
(4)
Isolated
(5)
, bipolar, differential, ±10V/0
…
20 mA, 11 bit and sign
For 0
…
20 mA, a jumper must be installed at terminals 17 and 18
(or 19 and 20)
88 kohm input impedance when configured for volt and 95.3 ohm for current
2
Analog In 1 (+)
3
Analog In 2 (–)
4
Analog In 2 (+)
5
Pot Common
–
For (+) and (–) 10V pot references
6
Analog Out 1 (–)
Single-ended bipolar (current output is not bipolar), ±10V/0
…
20mA, 11 bit and
sign, Voltage mode - limit current to 5 mA. Current mode - max. load is
400 ohms
7
Analog Out 1 (+)
8
Analog Out 2 (–)
9
Analog Out 2 (+)
10
HW PTC Input 1
–
1.8k ohm PTC, Internal 3.32 kohm pull-up resistor
11
Digital Out 1 – N.C.
(2)
Fault
Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5 A, Min. Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105 W
Max. Current: 3.5 A, Min. Load: 10 mA
12
Digital Out 1 Common
13
Digital Out 1 – N.O.
NOT Fault
14
Digital Out 2 – N.C.
NOT Run
15
Digital Out 2/3 Com.
16
Digital Out 3 – N.O.
Run
17
Current In Jumper
–
Analog In 1
Placing a jumper across terminals 17 and 18 (or 19 and 20) will configure that
analog input for current
18
19
Current In Jumper
–
Analog In 2
20
21
–10V Pot Reference
–
2 kohm minimum load
22
+10V Pot Reference
–
23
HW PTC Input 2
–
See above
24
+24V DC
–
Drive supplied logic input power
(6)
25
Digital In Common
–
26
24V Common
–
Common for internal power supply.
27
Digital In 1
(3)
Stop - CF
115V AC, 50/60 Hz - Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC, 5.7 mA
24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC, 10 mA DC Digital Input Impedance: 21 kohm
28
Digital In 2
Start
29
Digital In 3
Auto/Man.
30
Digital In 4
Speed Sel 1
31
Digital In 5
Speed Sel 2
32
Digital In 6/Hardware
Enable
Speed Sel 3
(1)
Important:
0-20 mA operation requires a jumper at terminals 17 and 18 (or 19 and 20). Drive damage may occur if jumper is not installed.
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied to drive and deenergize (drop out) when a fault or
alarm exists. Relays selected for other functions will energize only when that condition exists and will deenergize when condition is removed.
(3) A 10 k Ohm, 2 W burden resistor must be installed on each digital input when using a triac-type device. The resistor is installed between each digital input and
neutral/common.
(4) These inputs/outputs are dependant on a number of parameters. For more information, see Chapter 3, Programming and Parameters, in the PowerFlex 700 AC Drives User
Manual, publication
(5) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(6) 150 mA maximum Load. Not present on 115V versions.
16
32
1
17
Содержание Rockwell Automation PowerFlex 700 Series
Страница 1: ...PowerFlex 700 Drives to PowerFlex 750 Series Drives Migration Guide OriginalInstructions...
Страница 4: ...4 Rockwell Automation Publication PFLEX AP005B EN P May 2019 Table of Contents Notes...
Страница 54: ...54 Rockwell Automation Publication PFLEX AP005B EN P May 2019 Chapter 1 Drive Selection Considerations Notes...
Страница 71: ......