Programming and Parameters
3-13
T051-
T054
Options
(Cont.)
14
“Anlg1 InCtrl”
Selects Analog Input 1 control for the frequency
reference.
15
“Anlg2 InCtrl”
Selects Analog Input 2 control for the frequency
reference.
16
“MOP Up”
[Internal Freq] at the current
Accel rate if
[Speed Reference] is set to 1
“InternalFreq”. Default for A142 is 60 Hz.
17
“MOP Down”
Decreases the value of
[Internal Freq] at the
[Speed Reference] is set to 1
“InternalFreq”. Default for A142 is 60 Hz.
18
•
When active,
[Accel Time 2] and
[Decel
Time 2] are used for all ramp rates.
•
Can only be tied to one input.
for more information
on Accel/Decel selection.
19
“Current Lmt2”
[Current Limit 2] determines the drive
current limit level.
20
“Force DC”
If the drive is not running, applying this input causes the
drive to apply a DC Holding current (use
[DC Brake
Level], ignoring
[DC Brake Time] while the input is
applied.
21
“Mtr I-Lock 1”
Can be used as a protective motor interlock in Auxiliary
Motor Control mode. When programmed but not active,
input will prevent corresponding motor from operating.
Refer to
for details.
22
“Mtr I-Lock 2”
23
“Mtr I-Lock 3”
24
“Mtr I-Lock 4”
25
“Cmd Reverse”
When programmed and active the drive will run in the
reverse direction when started from the integral keypad.
31
“Logic In 1”
Input 1 used by digital output settings.
32
“Logic In 2”
Input 2 used by digital output settings.
36
“Damper Input”
•
When active, drive is allowed to run normally.
•
When inactive, drive is forced into sleep mode and is
prevented from accelerating to commanded speed.
(1)
This function may be tied to one input only.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......