Analog Inputs
7
Example 6
−
[Anlg In Config], bit 0 = “0” (Voltage)
−
[Speed Ref A Sel] = “Analog In 1”
−
[Speed Ref A Hi] = 60 Hz
−
[Speed Ref A Lo] = 0 Hz
−
[Analog In 1 Hi] = 5V
−
[Analog In 1 Lo] = 0V
This configuration is used when the input signal is 0-5 volts. Here, minimum input (0 Volts) represents 0
Hz and maximum input (5 Volts) represents 60 Hz. This allows full scale operation from a 0-5 volt
source.
Example 7
−
[Anlg In Config], bit 0 = “0” (Voltage)
−
[Torque Ref A Sel] = “Analog In 1”
−
[Torque Ref A Hi] = 200%
−
[Torque Ref A Lo] = 0%
−
[Torque Ref A Div] = 1 (PowerFlex 700VC Only)
This configuration is used when the input signal is 0-10 volts. The minimum input of 0 volts represents
a torque reference of 0% and maximum input of 10 volts represents a torque reference of 200%.
1
2
3
4
5
6
6
0
12
18
Output Hertz
Input Volts
24
30
36
42
48
54
60
2
4
6
8
10
12
20
0
40
60
Torque Ref %
Input Volts
80
100
120
140
160
180
200